For RWFs open longer than 24 hours, a manual comparison test
must be conducted every 24 hours.
Electronic data logging must be in increments of ≤15 minutes.
6.3.2.2.7 Charts (10)
HALOGEN analyzer-chart recorder charts must be initialed, dated,
and changed daily.
Strip recorder charts must be initialed and dated daily and 24-hour
increments must be indicated.
Dual-scale HALOGEN analyzer-chart recorder charts used in
RWFs must be able to measure the full range of HALOGEN/pH of
the facility type to which the chart is installed; for example,
chlorine/bromine to 10.0 MG/L (ppm) and pH 0-14 for
WHIRLPOOL SPAS.
6.3.2.2.8 Logs (10)
Logs and charts must contain notations outlining actions taken
when the free HALOGEN residual or pH levels are outside of the
acceptable ranges in this manual.
Additionally, records must include any major maintenance work
on the filtration and halogenation systems and UV
DISINFECTION systems.
A written or electronic log of RWF filter inspection results,
granular filter sedimentation test results, backwashing frequency
and length of backwashing, and date and time of water dumping
must be available for review during inspections.
6.3.2.2.9 Retention (10)
Logs and charts must be retained for 12 months and must be
available for review during inspections.
6.4 Whirlpool Spas and Spa Pools
6.4.1 Public Operations
6.4.1.1 Filters
6.4.1.1.1 Replacement (10)
At least one replacement cartridge or canister-type filter must be
available.
6.0 Recreational Water Facilities (RWFs); 73