Page 105 - Vessel Sanitation Program 2018 Operations Manual
P. 105
VSP 2018 Operations Manual
DISINFECTION must be accomplished with an appropriate HALOGEN-
based DISINFECTANT at 10 ppm for 60 minutes, or an equivalent CT
VALUE.
6.6.1.2 Maintenance (10)
Manufacturer’s operation and maintenance instructions must be available
to personnel who service the units.
6.6.1.3 Records (10)
A record must be maintained outlining the frequency of cleaning and
DISINFECTION. The record must include the type, concentration, and
contact time of the DISINFECTANT.
Records must be retained on the vessel for 12 months.
6.7 Individual Hydrotherapy Pools
6.7.1 Maintenance
6.7.1.1 Cleaning (10)
Individual hydrotherapy pools must be cleaned and disinfected, including
associated recirculation systems, between customers. DISINFECTION
must be accomplished with an appropriate HALOGEN-based
DISINFECTANT at 10 ppm for 60 minutes, or an equivalent CT VALUE.
6.7.1.2 Maintenance (10)
Manufacturer’s operation and maintenance instructions must be available
to personnel who service the units.
6.7.1.3 Records (10)
A record must be maintained outlining the frequency of cleaning and
DISINFECTION. The record must include the type, concentration, and
contact time of the DISINFECTANT.
Records must be retained on the vessel for 12 months.
6.8 Safety
6.8.1 RWFs
6.8.1.1 Signs and Markings
6.8.1.1.1 General RWF Signs (10)
Safety signs must be provided for all RWFs except BABY-ONLY
WATER FACILITIES.
6.0 Recreational Water Facilities (RWFs); 76