Page 105 - Vessel Sanitation Program 2018 Operations Manual
P. 105

VSP 2018 Operations Manual



                                     DISINFECTION must be accomplished with an appropriate HALOGEN-
                                     based DISINFECTANT at 10 ppm for 60 minutes, or an equivalent CT
                                     VALUE.


                          6.6.1.2    Maintenance (10)
                                     Manufacturer’s operation and maintenance instructions must be available
                                     to personnel who service the units.

                          6.6.1.3    Records (10)

                                     A record must be maintained outlining the frequency of cleaning and
                                     DISINFECTION. The record must include the type, concentration, and
                                     contact time of the DISINFECTANT.


                                     Records must be retained on the vessel for 12 months.

                   6.7        Individual Hydrotherapy Pools

                       6.7.1   Maintenance

                          6.7.1.1    Cleaning (10)

                                     Individual hydrotherapy pools must be cleaned and disinfected,  including
                                     associated recirculation systems, between customers. DISINFECTION
                                     must be accomplished with an appropriate HALOGEN-based
                                     DISINFECTANT at 10 ppm for 60 minutes, or an equivalent CT VALUE.

                          6.7.1.2    Maintenance (10)
                                     Manufacturer’s operation and maintenance instructions must be available
                                     to personnel who service the units.

                          6.7.1.3    Records (10)
                                     A record must be maintained outlining the frequency of cleaning and
                                     DISINFECTION. The record must include the type, concentration, and
                                     contact time of the DISINFECTANT.


                                     Records must be retained on the vessel for 12 months.

                   6.8        Safety

                       6.8.1   RWFs


                          6.8.1.1    Signs and Markings

                              6.8.1.1.1     General RWF Signs (10)
                                            Safety signs must be provided for all RWFs except BABY-ONLY
                                            WATER FACILITIES.