                   13.6       Potable Water Pipe and System Disinfection Method Examples
                   (Nonemergency)
                              Examples in this section relate to nonemergency situations. In an emergency, see
                              section 5.3.4.1.4 for concentration and contact time.


                              To achieve the proper DISINFECTION of a section of pipe being replaced,
                                 •   Fill the pipe with 50 MG/L (ppm) of free residual HALOGEN, cap on
                                     both ends, and let it sit for 4 hours OR Place small sections of pipes in a
                                     large container filled with 50 MG/L (ppm) of free residual HALOGEN for
                                     4 hours.
                                 •   Drain and flush disinfected parts of the system with POTABLE WATER.


                              To achieve the proper DISINFECTION of a section of pipe already installed on
                              part of the distribution system,
                                 1. Install temporary shut-off valves at each end of the new section.
                                 2. Close the valves.
                                 3. Inject 50 MG/L (ppm) of free residual HALOGEN through a temporary
                                     injection port.
                                 4. Let it stand for 4 hours.
                                 5. Drain and flush disinfected parts of the system with POTABLE WATER.














































                       Annex 13.6: Potable Water Pipe and System Disinfection Method Examples; 188