Page 89 - Vessel Sanitation Program 2018 Operations Manual
P. 89

VSP 2018 Operations Manual




                                            BACKFLOW PREVENTION DEVICES must be installed when
                                            AIR GAPS are impractical or when water under pressure is
                                            required. Provide an AIR GAP for the atmospheric vent of all
                                            BACKFLOW PREVENTION DEVICES.

                                            A mechanical BACKFLOW PREVENTION DEVICE must have
                                            an atmospheric vent.

                              5.7.1.2.2     2X Diameter (08)
                                            AIR GAPS must be at least twice the diameter of the delivery
                                            fixture opening and a minimum of 25 millimeters (1 inch).

                              5.7.1.2.3     Flood-Level Rim (08)
                                            An ATMOSPHERIC VACUUM BREAKER must be installed at
                                            least 150 millimeters (6 inches) above the flood-level rim of the
                                            fixtures.

                              5.7.1.2.4     After Valve (08)
                                            An ATMOSPHERIC VACUUM BREAKER must be installed
                                            only in the supply line on the discharge side of the last control
                                            valve.

                              5.7.1.2.5     Continuous Pressure (08)
                                            A CONTINUOUS PRESSURE-type BACKFLOW
                                            PREVENTION DEVICE must be installed when a valve is located
                                            downstream from the BACKFLOW PREVENTION DEVICE.


                              5.7.1.2.6     Backflow Prevention Devices (08)
                                            BACKFLOW PREVENTION DEVICES must be provided on all
                                            fixtures using POTABLE WATER and that have submerged inlets.


                              5.7.1.2.7     Vacuum Toilets (08)
                                            An ATMOSPHERIC VACUUM BREAKER must be installed on a
                                            POTABLE WATER supply connected to a vacuum toilet  system.
                                            An ATMOSPHERIC VACUUM BREAKER must be located on
                                            the discharge side of the last control valve (flushing device).

                              5.7.1.2.8     Diversion Valves (08)
                                            Lines to divert POTABLE WATER to other systems by valves or
                                            interchangeable pipe fittings must have an AIR GAP after the
                                            valve.