                          6.3.1.2    Filtration Systems

                              6.3.1.2.1     Filtered (10)
                                            Recirculated RWF water must be filtered.

                              6.3.1.2.2     Filter Backwash and Cleaning (10)

                                            Filter pressure differentials must be monitored. Granular filter
                                            media must be backwashed until the water viewed through a sight
                                            glass runs clear and at the following frequency:
                                                •  WHIRLPOOL SPA and SPA POOL: every 72 hours, or
                                                   sooner if the WHIRLPOOL SPA is drained.
                                                •  BABY-ONLY WATER FACILITY: daily.
                                                •  All other RWFs: at a frequency recommended by the
                                                   manufacturer.

                                            For automatic backwashing systems, an individual must be present
                                            in the filter room to ensure that backwashing is repeated as
                                            necessary until the water runs clear.

                                            Cartridge filters must be cleaned according to the manufacturer’s
                                            recommendations.

                                            A written or electronic record of the filter backwashing and
                                            cleaning must be available for review during inspections.

                              6.3.1.2.3     Granular Filter Inspection, Core Sample Test, and Filter
                              Change (10)
                                            Granular filter media must be examined for channels, mounds, or
                                            holes. A core sample of the filter media must be inspected for
                                            excessive organic material accumulation using a recommended
                                            sedimentation method.


                                            Inspections and sedimentation tests must be conducted quarterly
                                            for all RWFs.


                                            Inspection method:
                                            Drain the water from the filter housing and inspect the
                                            granular filter for channels, mounds, or holes.


                                            Core sample method:
                                                1. After inspection, take a sand sample from the filter core
                                                   and place it in a clear container. A core sample can be
                                                   taken by inserting a rigid hollow tube or pipe into the
                                                   filter  media.
                                                2. Add clean water to the container, cover, and shake.
                                                3. Allow the container to rest undisturbed for 30 minutes.



                                        6.0 Recreational Water Facilities (RWFs); 66