                                                4. Consider media replacement if after 30 minutes of
                                                   settling, a measurable layer of  sediment is within or on
                                                   top of the filter media or fine, colored particles are
                                                   suspended in the water. This condition can mean the
                                                   organic loading may be excessive.

                                            Granular filter media for WHIRLPOOL SPAS and SPA POOLS
                                            must be changed based on the inspection and sedimentation test
                                            results or every 12 months, whichever is more frequent. For all
                                            other RWFs, granular filter media must be changed based on the
                                            inspection and sedimentation results or per the manufacturer’s
                                            recommendations, whichever is more frequent.

                                            Results of both the filter inspection and sedimentation test must be
                                            recorded.

                              6.3.1.2.4     Cartridge Filter Inspection and Filter Change (10)
                                            Cartridge or canister-type filters must be inspected weekly for
                                            WHIRLPOOL SPAS and SPA POOLS. For all other RWFs,
                                            cartridge filters must be inspected every 2 weeks, or in accordance
                                            with the manufacturer’s recommendation, whichever is more
                                            frequent.

                                            The filters must be inspected for cracks, breaks, damaged
                                            components, and excessive organic accumulation. Cartridge or
                                            canister-type filters must be changed based on the inspection
                                            results, or as recommended by the manufacturer, whichever is
                                            more frequent.

                                            At least one replacement cartridge or canister-type filter must be
                                            available.

                              6.3.1.2.5     Other Filter Media (10)
                                            Inspect and change filters based on the manufacturer’s
                                            recommendations.

                              6.3.1.2.6     Filter Housing Cleaning and Disinfection (10)
                                            The filter housing must be cleaned, rinsed, and disinfected before
                                            the new filter media is placed in it. DISINFECTION must be
                                            accomplished with an appropriate HALOGEN-based
                                            DISINFECTANT. At a minimum, a 50-ppm solution for 1 minute,
                                            or equivalent CT VALUE, must be used. Records must be
                                            maintained on all inspection and cleaning procedures.

                                            The filter housing must be cleaned, rinsed, and disinfected each
                                            time the filter media—including cartridge filter—is changed.