Page 163 - Programmable Logic Controllers, Fifth Edition
P. 163

involves pumping fluid from tank A to tank B. The opera-
               tion of the process can be summarized as follows:
                 •  Before starting, PS1 must be closed.                                                   Cam-operated
                                                                                                           contact
                 •  When the start button is pushed, the pump starts.
                    The button can then be released and the pump con-
                    tinues to operate.
                 •  When the stop button is pushed, the pump stops.                                        Motor-driven
                                                                                                           cam
                 •  PS2 and PS3 must be closed 5 s after the pump starts.
                    If either PS2 or PS3 opens, the pump will shut off
                    and will not be able to start again for another 14 s.  Figure 7-26  Electromechanical retentive timer.

               7.5  Retentive Timer
                                                                     similar to the nonretentive on-delay timer (TON), with one
               A retentive timer accumulates time whenever the device   major exception—a retentive timer reset (RES) instruction.
               receives power, and it maintains the current time should   Unlike the TON, the RTO will hold its accumulated value
               power be removed from the device. When the timer ac-  when the timer rung goes false and will continue timing
               cumulates time equal to its preset value, the contacts of the   where it left off when the timer rung goes true again. This
               device change state. Loss of power to the timer after reach-  timer must be accompanied by a timer reset instruction to
               ing its preset value does not affect the state of the contacts.   reset the accumulated value of the timer to 0. The RES in-
               The retentive timer must be intentionally reset with a sepa-  struction is the only automatic means of resetting the accu-
               rate signal for the accumulated time to be reset and for the   mulated value of a retentive timer. The RES instruction has
               contacts of the device to return to its nonenergized state.  the same address as the timer it is to reset. Whenever the
                  Figure  7-26 illustrates the action of a motor-driven,   RES instruction is true, both the timer accumulated value
               electromechanical retentive timer used in some appliances.   and the timer done bit (DN) are reset to 0. Figure 7-27
               The shaft-mounted cam is driven by a motor. Once power   shows a PLC program for a retentive on-delay timer. The
               is applied, the motor starts turning the shaft and cam. The   operation of the program can be summarized as follows:
               positioning of the lobes of the cam and the gear reduction
               of the motor determine the time it takes for the motor to   •  The timer will start to time when time pushbutton
               turn the cam far enough to activate the contacts. If power is   PB1 is closed.
               removed from the motor, the shaft stops but does not reset.  •  If the pushbutton is closed for 3 s and then opened
                  A PLC retentive timer is used when you want to retain   for 3 s, the timer accumulated value will remain
               accumulated time values through power loss or the change   at 3 s.
               in the rung state from true to false. The PLC-programmed   •  When the time pushbutton is closed again, the timer
               retentive on-delay timer (RTO) is programmed in a manner   picks up the time at 3 s and continues timing.



                                       Inputs                Ladder logic program           Output
                                 L1                                                                  L2
                                   Reset
                                                    PB2                    T4:2
                                           PB2                             RES
                                    Time                                                 PL
                                                     PB1
                                            PB1             RTO
                                                            RETENTIVE TIMER ON   EN
                                                            Timer          T4:2
                                                            Time Base       1.0  DN
                                                            Preset           9
                                                            Accumulated      0

                                                     T4:2                  PL


                                                     DN
                                 Figure 7-27  Retentive on-delay timer program.



               144        Chapter 7  Programming Timers







          pet73842_ch07_131-155.indd   144                                                                              05/11/15   4:22 PM
   158   159   160   161   162   163   164   165   166   167   168