Page 307 - Programmable Logic Controllers, Fifth Edition - Mobile version
P. 307

associated wiring operate according to specifications. Be-
                        AC or DC                                     the PLC, the ladder logic program, the I/O devices, and all
                      output module                                  fore commissioning any control system, you should have
                                               MOV
                        VAC/VDC  +DC or L1                           a good understanding of how the control system operates
                         OUT 0                                       and how the various components interact. The following
                         OUT 1                                       are general steps to be followed when commissioning a
                         OUT 2                                       PLC system:
                         OUT 3
                                            Inductive load
                         OUT 4                                         •  Before applying power to the PLC or the input
                         OUT 5                                            devices, disconnect or otherwise isolate any output
                         OUT 6                                            device that could potentially cause damage or injury.
                         OUT 7                                            Typically this precaution would pertain to outputs that
                          COM
                                DC Com or L2                              cause movement such as starting a motor or operating
                                                                          a valve.
               Figure 13-13  Metal oxide varistor (MOV) surge
               suppressor.                                             •  Apply power to the PLC and input devices. Measure
                                                                          the voltage to verify that rated voltage is being
                                                                          applied.
               diodes connected back-to-back. The operation of an MOV
               can be summarized as follows:                           •  Examine the PLC’s status indicator lights. If power
                                                                          is properly applied, the power indicator should be
                 •  The device acts as an open circuit until the volt-    on, and there should be no fault indication. If the
                    age across it in either direction exceeds its rated   PLC does not power up properly, it may be faulty.
                    value.                                                PLCs rarely fail, but if they do fail, it usually
                 •  Any greater voltage peak instantly makes the device   happens immediately upon powering up.
                    act like a short circuit that bypasses this voltage   •  Verify that you have communication with the PLC
                    away from the rest of the circuit.                    via the programming device that is running the PLC
                                                                          programming software.
               13.6  Program Editing                                   •  Place the PLC in a mode that prevents it from
               and Commissioning                                          energizing its output circuits. Depending on the
                                                                          make of the PLC, this mode may be called disable,
               After you have entered the rungs for your program, you     continuous test, or single-scan mode. This mode
               may need to modify them. Editing is simply the ability to   will allow you to monitor input devices, execute
               make changes to an existing program through a variety of   the program, and update the output image file while
               editing functions. Using the editing function, instructions   keeping the output circuits de-energized.
               and rungs can be added or deleted; addresses, data, and
               bits can be changed. Again, the editing format varies with   •  Manually activate each input device, one at a
               different manufacturers and PLC models.                    time, to verify that the PLC’s input status lights
                  Today, most PLC programming software is Microsoft       turn on and off as expected. Monitor the associ-
               Windows based, so if you are familiar with Windows and     ated condition instruction to verify that the input
               know how to point and click with a mouse, you should       device corresponds to the correct program  address
               have no problem editing a program. In general, both in-    and that the instruction turns true or false as
               structions and rungs are selected simply by clicking on    expected.
               them with the left mouse button. Double clicking with the   •  Manually test each output. One way you can do this
               left mouse button allows you to edit an instruction’s ad-  is by applying power to the terminal where the out-
               dress, whereas right clicking displays a pop-up menu of    put device is wired. This test will check the output
               related editing commands. If you want to include addi-     field device and its associated wiring.
               tional explanation of a symbol or address, you can place   •  After verifying all inputs, outputs, and program ad-
               an address description on your ladder rung directly above   dresses, verify all preset values for counters, timers,
               the symbol. To add a page or rung comment, right click     and so on.
               on the rung number to which you wish to add the page or   •  Reconnect any output devices that may have been
               rung comment.                                              disconnected and place the PLC in the run mode.
                  Preparing a control process for start-up, also called   Test the operation of all emergency stop buttons and
               commissioning, involves a series of tests to ensure that   the total system operation.



               288        Chapter 13  PLC Installation Practices, Editing, and Troubleshooting







          pet73842_ch13_281-304.indd   288                                                                              03/11/15   7:22 PM
   302   303   304   305   306   307   308   309   310   311   312