Page 5 - Cannon MiniDataCenter
P. 5
Cannon Cool
Mini Data Centre Side Mount Cooling unit
Air-Water Heat Exchanger Specification
Characteristics Per Side Mount Cooling Unit
Cooling Capacity 0 - 30 Kw *depending on data center conditions
Water Flow Rate 30-75 L/min
Water Temp Flow 42U/2070 mm can be used with 45,47,52u cabinet
Water Temp Return 199 mm with the introduction of a base plinth
Height 1200 mm
Width 100-240 ~Vac ~ 47 - 63Hz
Depth
Power Supply 650W full load, (auto soft start).
Max. Power consumption
490W, (10W minimum).
Typical Power consumption (75%)
IEC C14 inlet, 3M -LSOH cable, 4-10A (240-110)
Electrical Connection
Refrigerant Water / Glycol, 20% mix recomended
Hydraulic Circuit Max. Pressure
Air Flow Rate 6 bar, nominal 2 bar. (0.5 bar pressure drop)
Air Temperature Range
1650 - 5100 m /h (1000 -3000 cfm)
Water connections (via base) (10MM CONDENSATE DRAIN,
1" BSPF. TO 3M PVC TUBE.)
CONDENSATE PUMP Max flow rate 20 l/h
Max suction head 2 m
Max discharge head 6 m
Temperature/Humidity sensors 10 off temperature sensors 4 air @ front,4 air @ rear ,1 humidity
Hot Swap Fans 1 water in & 1 water out , as std ( max of 16 temps per chiller)
6 off hot swap 48v dc fan cassettes
Standalone or Remote monitoring Remote Monitoring control and snmp alarms via Cannon Guard
local walk by status display with LCD and flashing alarms
Noise Level
Noise Level @ 50% load 62 dB(A)
Noise Level @ 75% load 70 dB(A)
Noise Level @ 100% load 80 dB(A)
Weight 150kg (dry weight) 165kg (wet)
Colour RAL 9002 Grey / 9005 Black
DC0656 -MDC-SMCU 5 of 11
TITLE 5/03/11
Mini Datacenter Side Mount Cooling unit