Page 5 - Cannon MiniDataCenter
P. 5

Cannon Cool

       Mini Data Centre Side Mount Cooling unit

       Air-Water Heat Exchanger Specification

       Characteristics                  Per Side Mount Cooling Unit
       Cooling Capacity                 0 - 30 Kw *depending on data center conditions
       Water Flow Rate                  30-75 L/min

       Water Temp Flow                  42U/2070 mm  can be used with 45,47,52u cabinet
       Water Temp Return                199 mm       with the introduction of a base plinth
       Height                           1200 mm

       Width                            100-240 ~Vac ~ 47 - 63Hz
       Depth
       Power Supply                     650W full load, (auto soft start).
       Max. Power consumption
                                        490W, (10W minimum).
       Typical Power consumption (75%)
                                        IEC C14 inlet, 3M -LSOH cable, 4-10A (240-110)
       Electrical Connection
       Refrigerant                      Water / Glycol, 20% mix recomended
       Hydraulic Circuit Max. Pressure
       Air Flow Rate                    6 bar, nominal 2 bar. (0.5 bar pressure drop)
       Air Temperature Range
                                        1650 - 5100 m /h (1000 -3000 cfm)

       Water connections (via base)                      (10MM CONDENSATE DRAIN,

                                        1" BSPF. TO 3M PVC TUBE.)

                                        CONDENSATE PUMP Max flow rate 20 l/h
                                                                    Max suction head 2 m

                                                     Max discharge head 6 m

       Temperature/Humidity sensors     10 off temperature sensors 4 air @ front,4 air @ rear ,1 humidity
       Hot Swap Fans                    1 water in & 1 water out , as std ( max of 16 temps per chiller)

                                        6 off hot swap 48v dc fan cassettes

       Standalone or Remote monitoring Remote Monitoring control and snmp alarms via Cannon Guard
                                                                                local walk by status display with LCD and flashing alarms

       Noise Level

       Noise Level @ 50% load           62 dB(A)

       Noise Level @ 75% load           70 dB(A)
       Noise Level @ 100% load          80 dB(A)
       Weight                           150kg (dry weight) 165kg (wet)
       Colour                           RAL 9002 Grey / 9005 Black

DC0656 -MDC-SMCU                        5 of 11

TITLE                                                                                                                                      5/03/11

Mini Datacenter Side Mount Cooling unit