Page 7 - Cannon MiniDataCenter
P. 7
Cannon Cool
Mini Data Centre Side Mount Cooling unit
Air-Water Heat Exchanger Performance Guidelines
Sensible Cooling Supply Water Water Flow Return Water Water pressure Air off Coil (DB) Air On Coil (DB) Temperature Air Flow Per
Capacity Temperature Rate l/s (l/m)
Drop Kpa (bar) KW CFM
KW (BTU/hr)
28 (95623) 1.00 (60) 28.0 (0.28) 107 (181)
28 (95623) 1.00 (60) 28.0 (0.28) 107 (181)
28 (95623) 1.25 (75) 37.0 (0.37) 107 (181)
28 (95623) 1.25 (75) 37.0 (0.37) 107 (181)
30 (102453) 1.25 (75) 37.0 (0.37) 100 (170)
Note: all above values are based on air flow at full speed and the Cannon Air-lokk fitted to maximize
airflow efficiency,in the rack.
*Data center /Room conditions:
Humidity is directly related to the temperature, so monitoring temperature and humidity together is critical.The
Cannon Mini Data Centre will monitor temperature and humidity and provide feedback via snmp or local lcd,
Keeping your data center or Cannon cabinet humidity levels between 30% and 55% is recommended. While
individual server manufactures recommendations vary for humidity & temperature) .The Cannon Mini Data Centre is
an air to water heat exchanger and does not regulate humidity; it is recommended that external dehumidifier /
humidifier system be in place to manage humidity within the data centre or room. These parameters must be
achieved before system Start up to avoid excess condensate causing the Mini Data Centre to send alarms
(see install and maintenance manual for full room preparation).
DC0656 -MDC-SMCU 7 of 11
TITLE 5/03/11
Mini Datacenter Side Mount Cooling unit