                  Mini Data Centre Side Mount Cooling unit

                  Air-Water Heat Exchanger Performance Guidelines

Sensible Cooling  Supply Water Water Flow     Return Water  Water pressure Air off Coil (DB) Air On Coil (DB) Temperature Air Flow Per
Capacity          Temperature Rate l/s (l/m)
                                                            Drop Kpa (bar)  KW CFM
KW (BTU/hr)

20 (68302)        0.66 (40)                                 15.9 (0.159)    150 (254)
20 (68302)        0.66 (40)                                 15.9 (0.159)    150 (254)
20 (68302)        0.66 (40)                                 15.9 (0.159)    150 (254)
20 (68302)        0.83 (50)                                 22.0 (0.22)     150 (254)
20 (68302)        0.83 (50)                                 22.0 (0.22)     150 (254)
20 (68302)        0.83 (50)                                 22.0 (0.22)     150 (254)
20 (68302)        1.00 (60)                                 28.0 (0.28)     150 (254)
20 (68302)        1.00 (60)                                 28.0 (0.28)     150 (254)
20 (68302)        1.00 (60)                                 28.0 (0.28)     150 (254)
20 (68302)        1.25 (75)                                 37.0 (0.37)     150 (254)
20 (68302)        1.25 (75)                                 37.0 (0.37)     150 (254)

25 (85378)        0.66 (40)                                 15.9 (0.159)    125 (212)
25 (85378)        0.66 (40)                                 15.9 (0.159)    125 (212)
25 (85378)        0.66 (40)                                 15.9 (0.159)    125 (212)
25 (85378)        0.83 (50)                                 22.0 (0.22)     125 (212)
25 (85378)        0.83 (50)                                 22.0 (0.22)     125 (212)
25 (85378)        0.83 (50)                                 22.0 (0.22)     125 (212)
25 (85378)        1.00 (60)                                 28.0 (0.28)     125 (212)
25 (85378)        1.00 (60)                                 28.0 (0.28)     125 (212)
25 (85378)        1.00 (60)                                 28.0 (0.28)     125 (212)
25 (85378)        1.25 (75)                                 37.0 (0.37)     125 (212)
25 (85378)        1.25 (75)                                 37.0 (0.37)     125 (212)

DC0656 -MDC-SMCU                              6 of 11

TITLE                                                                       5/03/11

Mini Datacenter Side Mount Cooling unit
   1   2   3   4   5   6   7   8   9   10   11