Page 6 - Cannon MiniDataCenter
P. 6
Cannon Cool
Mini Data Centre Side Mount Cooling unit
Air-Water Heat Exchanger Performance Guidelines
Sensible Cooling Supply Water Water Flow Return Water Water pressure Air off Coil (DB) Air On Coil (DB) Temperature Air Flow Per
Capacity Temperature Rate l/s (l/m)
Drop Kpa (bar) KW CFM
KW (BTU/hr)
20 (68302) 0.66 (40) 15.9 (0.159) 150 (254)
20 (68302) 0.66 (40) 15.9 (0.159) 150 (254)
20 (68302) 0.66 (40) 15.9 (0.159) 150 (254)
20 (68302) 0.83 (50) 22.0 (0.22) 150 (254)
20 (68302) 0.83 (50) 22.0 (0.22) 150 (254)
20 (68302) 0.83 (50) 22.0 (0.22) 150 (254)
20 (68302) 1.00 (60) 28.0 (0.28) 150 (254)
20 (68302) 1.00 (60) 28.0 (0.28) 150 (254)
20 (68302) 1.00 (60) 28.0 (0.28) 150 (254)
20 (68302) 1.25 (75) 37.0 (0.37) 150 (254)
20 (68302) 1.25 (75) 37.0 (0.37) 150 (254)
25 (85378) 0.66 (40) 15.9 (0.159) 125 (212)
25 (85378) 0.66 (40) 15.9 (0.159) 125 (212)
25 (85378) 0.66 (40) 15.9 (0.159) 125 (212)
25 (85378) 0.83 (50) 22.0 (0.22) 125 (212)
25 (85378) 0.83 (50) 22.0 (0.22) 125 (212)
25 (85378) 0.83 (50) 22.0 (0.22) 125 (212)
25 (85378) 1.00 (60) 28.0 (0.28) 125 (212)
25 (85378) 1.00 (60) 28.0 (0.28) 125 (212)
25 (85378) 1.00 (60) 28.0 (0.28) 125 (212)
25 (85378) 1.25 (75) 37.0 (0.37) 125 (212)
25 (85378) 1.25 (75) 37.0 (0.37) 125 (212)
DC0656 -MDC-SMCU 6 of 11
TITLE 5/03/11
Mini Datacenter Side Mount Cooling unit