Page 646 - Basic Electrical Engineering
P. 646
Iron, friction and windage, and field copper = No-load input − I ao 2 R a
losses
2
= 1760 − 6 × 0.1
= 1760 − 3.6
= 1756.4 W
These are constant losses.
Note that I ao 2 R loss in the armature at no load is very small.
a
The generator is rated at 50 kW and 220 V.
The generator output current at full load.
2
Full-load armature Copper loss = I R a
a
= (229.2) × 0.1
2
= 5253 W
This is the variable loss.
Figure 7.27
Efficiency of the generator in percentage = Output/(Output + Constant losses
+ Variable loss)