Page 33 - DMcatalogue2017
P. 33
Low voltage AC drives
ABB micro drives
ACS150 – Ratings, types, voltages and prices
200/240 V, 1-phase supply voltage
Nominal Nominal output Max output Frame Fuse A Heat Cooling Type List Price
current Type gG dissipation requirements
3
kW A A W m /h £
0.37 2.4 4.2 R0 10 25 +Nat Vent ACS150-01E-02A4-2 £105
0.75 4.7 8.2 R1 16 46 24 ACS150-01E-04A7-2 £123
1.1 6.7 11.7 R1 20 71 24 ACS150-01E-06A7-2 £155
1.5 7.5 13.1 R2 25 73 21 ACS150-01E-07A5-2 £174 4
2.2 9.8 17.2 R2 35 96 21 ACS150-01E-09A8-2 £208
+ Ensure enough space around the unit - refer to the User’s Manual for details
200/240 V, 3-phase supply voltage
3-phase, 240 V is available for customers supplying the North American market. Please enquire for details.
380/480 V, 3-phase supply voltage
Nominal Nominal output Max output Frame Fuse A Heat Cooling Type List Price
current Type gG dissipation requirements
kW A A W m /h £
3
0.37 1.2 2.1 R0 10 11 +Nat Vent ACS150-03E-01A2-4 £167
0.55 1.9 3.3 R0 10 16 +Nat Vent ACS150-03E-01A9-4 £177
0.75 2.4 4.2 R1 10 21 13 ACS150-03E-02A4-4 £193
1.1 3.3 5.8 R1 10 31 13 ACS150-03E-03A3-4 £212
1.5 4.1 7.2 R1 16 40 13 ACS150-03E-04A1-4 £231
2.2 5.6 9.8 R1 16 61 19 ACS150-03E-05A6-4 £331
3 7.3 12.8 R1 16 74 24 ACS150-03E-07A3-4 £398
4 8.8 15.4 R1 20 94 24 ACS150-03E-08A8-4 £453
+ Ensure enough space around the unit - refer to the User’s Manual for details
The drive can be fitted with the NEMA 1 kit for easy wall-mounting and convenient protection, see user interfaces in ABB machinery drive section, page 38.
Drives and controls, motors and mechanical power transmission catalogue 33