Page 18 - GuardII+ Series 4208 Platform PD User Manual
P. 18

PD Card Operation



              4.2.  PD Measurement Cycle

                        When performing PD measurements, the monitor will run through the following cycle:
                        •  Perform measurements on the User Range for all enabled PD inputs.

                        •  Perform measurements on the Auto Range for all enabled PD inputs.
                        •  Perform measurements on the Alert Range for all enabled PD inputs.

                        •  Update Operating Condition data.
                        •  Analyze  the  PD  data  for  any  Triggers  and/or  Alerts  that  occurred  in  this  set  of
                            measurements (refer to Section 4.6 for PD Trigger details).
                        •  Resolve any actions that occur, such as saving measurement data or activating the
                            Alert.
                        •  Update Modbus slave PD data.
                        The time that it takes to complete a PD measurement cycle depends on the number of
                     inputs that the monitor has:

                                     # of Input Pairs      PD Measurement Cycle Time
                                       3 (BUS only)                 ~ 17 minutes
                                     6 (PDA or SSC)                 ~ 32 minutes
                                       9 (SSC only)                 ~ 48 minutes
                                    12 (PDA or SSC)                 ~ 65 minutes


                                     NOTE:
                                     When  a  GuardII+  includes  other  technologies  such  as  magnetic  flux
                                     monitoring or endwinding vibration monitoring, the PD measurement cycle
                                     time  will  not  be  significantly  affected  by  these  other  monitoring
                                     technologies.


              4.3.  Measurement Ranges

                        GuardII+  runs  PD  measurements  on  three  different sensitivity  ranges  per  input; these
                     sensitivity ranges are referred to as User Range, Auto Range and Alert Range.

              4.3.1.  User Range

                        The User Range is selected during commissioning according to the PD levels at the time.
                     The purpose of this sensitivity is to provide a consistent trend of data from the current PD
                     levels until the PD increases beyond the User Range.  Once the User Range sensitivity is set,
                     GuardII+ will run measurements at that sensitivity until re-configured to a different sensitivity.
                     Each input of the monitor can have a different User Range sensitivity.
                        If the User Range of an input is disabled, then the Auto and Alert Ranges will also be
                     disabled for that input.