Page 48 - GuardII+ Series 4208 Platform PD User Manual
P. 48

Installation





















                                       Figure 5-16 12-Sensor SSC PD Card Connections

                                Termination Box Connection                  GuardII+ Connection
                             Left Terminals A Phase Endwinding                      EW 1
                                 Left Terminals A Phase Slot                       SLOT 1
                             Left Terminals B Phase Endwinding                      EW 2
                                 Left Terminals B Phase Slot                       SLOT 2
                             Left Terminals C Phase Endwinding                      EW 3
                                 Left Terminals C Phase Slot                       SLOT 3
                          Left-Center Terminals A Phase Endwinding                  EW 4
                              Left-Center Terminals A Phase Slot                   SLOT 4
                          Left-Center Terminals B Phase Endwinding                  EW 5
                              Left-Center Terminals B Phase Slot                   SLOT 5
                          Left-Center Terminals C Phase Endwinding                  EW 6
                              Left-Center Terminals C Phase Slot                   SLOT 6
                         Right-Center Terminals A Phase Endwinding                  EW 7
                             Right-Center Terminals A Phase Slot                   SLOT 7
                         Right-Center Terminals B Phase Endwinding                  EW 8
                             Right-Center Terminals B Phase Slot                   SLOT 8
                         Right-Center Terminals C Phase Endwinding                  EW 9
                             Right-Center Terminals C Phase Slot                   SLOT 9
                             Right Terminals A Phase Endwinding                    EW 10
                                 Right Terminals A Phase Slot                     SLOT 10
                             Right Terminals B Phase Endwinding                    EW 11
                                 Right Terminals B Phase Slot                     SLOT 11
                             Right Terminals C Phase Endwinding                    EW 12
                                Right Terminals C Phase Slot                      SLOT 12


              5.9.  External Reference Connections

                        An external synchronization connection is not always necessary; SSC installations require
                     an external synchronization, but typically BUS and PDA installations do not.  Typically, an
                     external reference source is built into the PD termination panel, although this may not be the
                     case at all sites.