Page 48 - GuardII+ Series 4208 Platform PD User Manual
P. 48
Installation
Figure 5-16 12-Sensor SSC PD Card Connections
Termination Box Connection GuardII+ Connection
Left Terminals A Phase Endwinding EW 1
Left Terminals A Phase Slot SLOT 1
Left Terminals B Phase Endwinding EW 2
Left Terminals B Phase Slot SLOT 2
Left Terminals C Phase Endwinding EW 3
Left Terminals C Phase Slot SLOT 3
Left-Center Terminals A Phase Endwinding EW 4
Left-Center Terminals A Phase Slot SLOT 4
Left-Center Terminals B Phase Endwinding EW 5
Left-Center Terminals B Phase Slot SLOT 5
Left-Center Terminals C Phase Endwinding EW 6
Left-Center Terminals C Phase Slot SLOT 6
Right-Center Terminals A Phase Endwinding EW 7
Right-Center Terminals A Phase Slot SLOT 7
Right-Center Terminals B Phase Endwinding EW 8
Right-Center Terminals B Phase Slot SLOT 8
Right-Center Terminals C Phase Endwinding EW 9
Right-Center Terminals C Phase Slot SLOT 9
Right Terminals A Phase Endwinding EW 10
Right Terminals A Phase Slot SLOT 10
Right Terminals B Phase Endwinding EW 11
Right Terminals B Phase Slot SLOT 11
Right Terminals C Phase Endwinding EW 12
Right Terminals C Phase Slot SLOT 12
5.9. External Reference Connections
An external synchronization connection is not always necessary; SSC installations require
an external synchronization, but typically BUS and PDA installations do not. Typically, an
external reference source is built into the PD termination panel, although this may not be the
case at all sites.
40
www.irispower.com