Page 99 - PBL614 IM/SM500F-EN SM500F ( WIRO)
P. 99

SM500F
Field mountable paperless recorder 7 Configuration
Specify the display range and units of the engineering value corresponding to the electrical high and low values, within the limits defined in Table 7.4:
     􏰺􏰤
    THC/RTD Type
°C
°F
Min.
 Max.
Min.
 Max.
 B
–18
1800
0
3270
E
–100
900
–140
1650
J
–100
900
–140
1650
K
–100
1300
–140
2350
L
–100
900
–140
1650
N
–200
1300
–325
2350
R&S
–18
1700
0
3090
T
–250
300
–400
570
Pt100
–200
600
–325
1100
Power 5/2
Power 3/2 Square Root Custom Linearizer 1 Custom Linearizer 2 Linear
–999 to +9999
                   Table 7.4 Limits of Engineering Ranges
Example – for an electrical input range of 4.0 to 20.0mA, representing a pressure range of 50 to 250 bar, set the 'Low' value to 50.0 and the 'High' value to 250.0.
Note.
 Select any of the engineering units pre-programmed into the recorder or select 'Custom' and enter user-defined units (6 characters max.). Refer to Appendix D, Table D.1, page 163 for a description of the pre-defined engineering units.
 The recorder can be configured to calculate the totalizer count rate automatically by ensuring that the engineering range unit of measurement selected for the channel to which the totalizer is assigned is a volumetric unit (i.e. quantity per unit of time, for example gallons per hour) – see page 107. If the recorder holds the relationship data between the selected measurement units and totalizer units, the count rate parameter is calculated and displayed automatically.
•1 If this parameter is changed, internally recorded data files are recreated and unarchived data is lost. IM/SM500F Rev. AA 97
 