Page 51 - +GF+ PPR Aquasystem Catalogue 2017_Neat
P. 51
Saddles Installation
Welding Parameter
Diameter Diameter Heating Heating Holding Cooling
pipe derivation time pipe time saddle time time
(mm) (mm) (sec) (sec) (sec) (min)
40 20 30 30 20 30
40 25 30 30 20 30
50 20 30 30 20 30
50 25 30 30 20 30
63 20 30 30 20 30
63 25 30 30 20 30
63 32 30 30 20 30
75 20 30 30 20 30
75 25 30 30 20 30
75 32 30 30 20 30
75 40 30 30 20 30
90 20 30 30 20 30
90 25 30 30 20 30
90 32 30 30 20 30
90 40 30 30 20 30
110 20 30 30 20 30
110 25 30 30 20 30
110 32 30 30 20 30
110 40 30 30 20 30
125 20 30 30 20 30
125 25 30 30 20 30
125 32 30 30 20 30
125 40 30 30 20 30
40 1/2” 30 30 20 30
40 3/4” 30 30 20 30
50 1/2” 30 30 20 30
50 3/4” 30 30 20 30
63 1/2” 30 30 20 30
63 3/4” 30 30 20 30
75 1/2” 30 30 20 30
75 3/4” 30 30 20 30
75 1” 30 30 20 30
90 1/2” 30 30 20 30
90 3/4” 30 30 20 30
90 1” 30 30 20 30
110 1/2” 30 30 20 30
110 3/4” 30 30 20 30
110 1” 30 30 20 30
125 1/2” 30 30 20 30
125 3/4” 30 30 20 30
125 1” 30 30 20 30
correct installation