EOS          90395-A-PHY-0002-Column feet assembly & setting



               7.  NOTE 1 - HEIGHT COMPENSATION – SHIMMING PLATES


                   a.  The system ships with a set of 4
                      aluminum plates that are used as
                      “shims”. Each shim is 5mm thick and
                      match the footprint of the Nivell
                      plates.


                   b.  Start by measuring the height
                      difference between Nivell plates with
                      respect to the floor. If the difference if

                      greater than 5mm, consider adding
                      metal shims underneath the lowest Nivell plate.  Each shimming plate adds/removes
                      approximately 5mm of height.

                   c.  Keep in mind that at this point, this is still just a rough approximation, the fine tuning of height

                      and levelness will come later in the process. However, the closer we are now in height and
                      levelness the easier it will be to fine-tune the columns later.


















                                IMPORTANT: Overall room floor levelness should be 2mm / m (0.024 in/ft).
                                Floor flatness of the gantry footprint should have a maximum of 5mm (0.20)

                                between highest and lowest points.
                                Try to use the least number of shims that gives you a height difference of
                                < 5mm.