Page 52 - puget sound energy community energy programs
P. 52
Chapter 4
Figure 25 Minimum dimensions of excavation requirements for small secondary handholes
PSE 1324 POLYETHELYNE HANDHOLE
PLAN VIEW
APPROX ELECTRIC
APPROX 13"
2" 24"
4' - 0"
PENTABOLT
LOCK COVER
5' - 0"
15”
SIDE VIEW
4" X 4"
KNOCKOUT
(2 PLACES)
APPROX 32" 17"
APPROX 23"
CONDUITS ENTER FROM BENEATH
AT ONE END OF HANDHOLE
PSE 1730 POLYETHELYNE HANDHOLE PLAN VIEW
APPROX ELECTRIC
APPROX 17"
2" 30"
4' - 5"
PENTABOLT
LOCK COVER
5' - 6"
18"
SIDE VIEW
4" X 4"
KNOCKOUT
(2 PLACES) 20"
APPROX 40"
APPROX 27"
CONDUITS ENTER FROM BENEATH
AT ONE END OF HANDHOLE
Electric Service Handbook 2017 — Single-Family Residential Projects 43