Chapter 5



               400 A self-contained services

                                  The meter base/socket required for a 120/240 V, 400 A service is called a Class
                                  320 meter base/socket (see Figures 30 and 31). It is larger than the 200 A meter
                                  base/socket, but it is still a self-contained meter base/socket. It can be installed on
                                  residences where the continuous current rating is 320 A or less.
                                  NOTE: If your structure requires more than 320 A of continuous current, you are
                                  required to install a CT service (refer to the 400 A current transformer (CT) services
                                  section in this chapter).

               Underground        In addition to the meter base/socket requirements listed earlier in this chapter,
                                  Class 320 meter bases/sockets for 400 A underground services shall:
                                  •   Be rated for 120/240 V and 320 A continuous current.
                                  •   Contain four meter jaws and one connection point for the neutral conductor.
                                  •   Contain a Class 320 manual block bypass (see Figure 30).
                                  •   Have lugs that will accept 350 MCM aluminum wire.
                                  •   Accept 3-inch steel or Schedule 40 or 80 conduit through a knockout in the
                                      bottom left corner or center of the enclosure.
                                  •   Have at least an 8-1/2-inch clearance between the bottom of the lugs and the
                                      bottom of the enclosure (see Figure 30).

               Figure 30          Typical arrangement of service conductors for underground class 320 meter base/
                                  socket




                                                                              METER
                                                                              BASE/SOCKET
                                                                              MUST BE
                                                                              GROUNDED
                                                                              PER NEC.

                                           BYPASS STUDS                        BYPASS STUDS
                                                               LOAD
                                                               LUGS
                                              LINE LUG                         LINE LUG



                                                                               NEUTRAL BLOCK
                                               8-1/2"
                                               MIN
                                                                                CUSTOMER
                                                                                WIRES



                                                                 3" RIGID STEEL OR PVC FOR 320 A
                                                                 RESIDENTIAL, CUSTOMER PROVIDED
                                                                 (MAY BE LOCATED IN THE BOTTOM
                                             PSE’S 4/0 OR        CORNER OPPOSITE THE NEUTRAL
                                                                 BLOCK OR CENTER OF THE ENCLOSURE)
                                              350 CABLE







               Electric Service Handbook 2017 — Single-Family Residential Projects                          51