Page 63 - puget sound energy community energy programs
P. 63

Chapter 5



               Figure 33           Single-phase CT mounting base



                                                           EUSERC 328A SHOWN
                                                                              CT MOUNTING BOLTS
                                         3/4"                 5"              TYPICAL 4 PLACES -
                                                                              SEE NOTE 3
                                      1-3/4"
                                                                                       1-3/8"

                                                             1-1/2"  1-1/2"        7/8"
                                                N

                               10-32 MACHINE SCREW                                     8-1/8"
                              & WASHER DRILLED AND
                                  TAPPED INTO BUS



                                                                                      1-3/8"
                                                   1-3/4"

                                                    3/4"             8" MIN          BUS MARKING “CT”
                                              CABLE TERM. BOLTS                      (TYPICAL 2 PLACES)
                                      (TYPICAL 4 PLACES - SEE NOTE 3)


                                                         INSULATING SUPPORT (SEE NOTE 1)
                                           2" MIN                         1/4"
                                          2-1/2" MAX

                                                                                         3-1/2"
                                     INSULATING
                                       BARRIER


                                   Notes:
                                  1.  Insulated supports shall be rated for the serving voltage and have sufficient
                                     mechanical strength for the application.
                                  2.  Mounting base accepts bar-type current transformers only.
                                   3.  Two 1/2-inch steel bolts shall be provided for each cable terminating position and
                                     each bolt shall be furnished with a spring washer and a nut. The spring washer
                                     may be either a cone-type (belleville) or a split-ring washer and a flat washer. Bolts
                                     shall be secured in place and spaced as shown. All parts shall be plated to prevent
                                     corrosion.

















               Electric Service Handbook 2017 — Single-Family Residential Projects                          54