Page 61 - Puret Sound Energy Hand Book 1218
P. 61

Chapter 5




               Overhead           •   In addition to the meter base/socket requirements listed earlier in this chapter,
                                      Class 320 meter bases/sockets for 400 A overhead services shall:
                                  •   Be rated for 120/240 V and 320 A continuous current.
                                  •   Contain four meter jaws and one connection point for the neutral conductor
                                      (see Figure 31).
                                  •   Contain a Class 320 manual block bypass.

               Figure 31          Typical arrangement of service conductors for overhead class 320 meter base/socket




                                                                  SERVICE CONDUCTORS
                                                                  TO WEATHERHEAD,
                                                                  CUSTOMER PROVIDED


                                                                                       NOTE: METER BASE/
                                                                                       SOCKET MUST BE
                                                                                       GROUNDED PER NEC.
                                                                                       NOTE: LINE LUGS SHALL
                                                                                       BE TURNED 180˚ TO ALLOW
                                                                                       PROPER INSERTION OF
                                         LINE LUG                         LINE LUG     WIRE AND TO KEEP FROM
                                                                                       BLOCKING BYPASS AREA.
                                      BYPASS STUDS                        BYPASS STUDS


                                         LOAD LUG                         LOAD LUG



                                                                          NEUTRAL BLOCK

                                                                            CUSTOMER
                                                                            WIRES





               Outbuildings       The metering requirements for 400 A services to outbuildings are the same as the
               (overhead or       metering requirements for 400 A services to single-family residential structures.
               underground
               service)





















               Electric Service Handbook 2017 — Single-Family Residential Projects                          52