Control of Industrial Major Accident Hazards (CIMAH) Report   Page       38
                                               Ranhill SAJ Sdn. Bhd.                    Revision      01
                                  Part D: Information on the Potential Major Accident   Date        Aug 2019


               Under  the  failure  event  of  “scrubber failure  (poor efficiency)”,  the  maximum
               consequence  distance  is  generally  dispersed  less  compared  to  “storage door
               opened”  due  to  the  time  travels  inside  the  system  prior  to  release  via  the  stack
               (release rate at 1kg/s).

               The major or small leak event with “scrubber failure” is not further analysed of the
               dispersion to the atmosphere. This is due to the fact that during the leak, the chlorine
               gas will be contained inside the store and diluted by air over time. The dilution will
               cause the concentration of chlorine gas over time to be significant. The release rate
               of this “diluted chlorine gas” via the stack of scrubber is below 1kg/s, with the 20%
               scrubber efficiency, will not able to generate appropriate dispersion contour.