Page 319 - E:\CloudStation\Project\1 DONE\Ranhill CIMAH\Flip Book\
P. 319

Control of Industrial Major Accident Hazards (CIMAH) Report   Page   39
 Ranhill SAJ Sdn. Bhd.      Revision       01
           Part D: Information on the Potential Major Accident   Date   Aug 2019


                            Accident   Location  Hazardous Substance  Event 1  Event 2
 Consequence Maximum Distance   Scenario  KT1  Chlorine  Rupture (Cylinder)  Door Opened
                             A1
 (m)                         B1    KT1     Chlorine  50mm Leak (Cylinder) Door Opened
                             C1    KT1     Chlorine  10mm Leak (Cylinder) Door Opened
 4000       3890.48          D2    KT2     Chlorine  Rupture (Drum)  Scrubber failure
                             E2    KT2     Chlorine  Rupture (Drum)  Door Opened
 3604.69                     F2    KT2     Chlorine  50mm Leak (Drum)  Door Opened
                             G2    KT2     Chlorine  10mm Leak (Drum)  Door Opened
 3500

 3000                          2888.3

 2500


 2000


 1500
 1159.94   1084.62
 1000
 596.28                                          612.68
 500
 257.71           286.61             214.53
 47.4   4.49   47.7   4.7   27.88   3.31   12.23   42.41   32.11   32.26   4.81
 0  10 (IDLH)  495 (50% fatality)  4827 (100% fatality)  10 (IDLH)  495 (50% fatality)  4827 (100% fatality)  10 (IDLH)  495 (50% fatality)  4827 (100% fatality)  10 (IDLH)  495 (50% fatality)  4827 (100% fatality)  10 (IDLH)  495 (50% fatality)  4827 (100% fatality)  10 (IDLH)  495 (50% fatality)  4827 (100% fatality)  10 (IDLH)  495








 A1  B1  C1  D2     E2                F2                G2
 KT1 WTP                   KT2 WTP
                                                     Concentration (ppm)
 Figure D.6.1.4: Consequence Maximum Distance of an Accident Event and the Acute Health Effects (IDLH, 50% fatality and 100% fatality)
   314   315   316   317   318   319   320   321   322   323   324