Page 342 - E:\CloudStation\Project\1 DONE\Ranhill CIMAH\Flip Book\
P. 342

Control of Industrial Major Accident Hazards (CIMAH) Report   Page       52
                                               Ranhill SAJ Sdn. Bhd.                    Revision      01
                                  Part D: Information on the Potential Major Accident   Date        Aug 2019



                  Location of the Plant       Location Specific       Maximum            Acceptance Criteria
                (in relation to the source of   Individual Risk     Distance from       (Within      (Residential,
                        release)              (fatality per year)    Source, (m)    Plant,1x10-5 per   1x10-6 per year)
                                                                                         year)

                                                         -6
              KT1 Chlorine Room                 8.16 x 10               5 m          Within Criterion     -



                                                         -6
              KT2 Chlorine Room                 6.79 x 10               5 m          Within Criterion     -



                                                         -6
              KT2 Chemical Building             6.79 x 10              10 m          Within Criterion     -


                                                         -7
              KT2 Administration Office         8.40 x 10              15 m          Within Criterion   Within Criterion



                                                         -7
              KT2 Guard House                   8.40 x 10              30 m          Within Criterion   Within Criterion


                                   Table D.6.2.2: Location Specific Individual Risk (LSIR)

                     Quantitative
                    Individual Risk            Criterion 1: Within Plant, 1x10-5 per year
                   1.00E-05
                                    8.16E-06
                   8.00E-06                        6.79E-06
                                                                    6.79E-06
                   6.00E-06


                   4.00E-06

                   2.00E-06                                                        8.40E-07   8.40E-07

                  0.00E+00
                            KT1 Chlorine Room KT2 Chlorine Room  KT2 Chemical  KT2 Administration  KT2 Guard House
                                                               Building         Office              Location
                               Figure D.6.2.2a: Location Specific Individual Risk by Location

                               Figure D.6.2.2a: Location Specific Individual Risk by Location