Page 54 - B8773-AEW-XX-XX-PP-A-0001_[P1]_Contractors Manual
P. 54

Health and S
                                                                                                                  Executive

                                                                                                                                                                                                         ACOP

The coldroom MUST incorporate an insulated and heated floor to avoid condensation problems
causing future damage to the floor below.

General            Must comply with all relevant legislation in force at the time of manufacture.
Temperature range
                   To be capable of maintaining the temperature in the range of 0 / +3 degrees
Dimensions         Celsius
Insulation         External dimensions as stated on project drawings.
Finishes
                   80mm thick zero ODP injected polyurethane.
                   External - white food safe laminate steel.
                   Internal - white food safe laminate steel to walls and ceilings.

Floor              The coldrom must have an insulated and heated floor to minimize the risk of
                   condensation below.

Door               Hinged to suit clear opening of 0.750m x 1.920m high, with locking fastener and
                   internal emergency release mechanism.

NOTE: Although sliding doors are available, these are NOT recommended due to the tendency for them to repeatedly  Guidance
come off the runners as a result of rough handling by staff.                                                      ACOP
PVC strip curtains for the door should be included as standard.

Light              The coldroom must be fitted with a suitable internal light and external switch, as
                   standard. An emergency light to comply with BS5839 should be supplied and
                   installed by the coldroom installer, in addition to the working light.

Shelving           Supply and install suitable 3 tier shelving, nominal size 1800 x 500mm, to fit under
                   the internal evaporator

Wall Spacers       Supply and install nom. 75mm x 75mm S/S top hat section spacers, to run the full
                   length of all internal walls EXCEPT the wall under the evaporator.

Equipment          Evaporator internally ceiling mounted. A condensate pump may be required
                   and should be priced as an optional extra.
                   External compressor unit in weather-proof housing and must be specified to be
                   very quiet in operation to avoid nuisance to neighbours when running. ( Sylensys
                   or similar)

Controls           filter/drier, sight glass etc.
                   Suction line insulated with Armaflex insulation.

Refrigerant        System to be leak checked, evacuated and charged with R134A refrigerant.

Wiring             Supplied from 20 amp single phase outlet provided by others.

Pricing            To include installation, commissioning, training, provision of operation and
                   maintenance manual and shelving

Warranty           Twelve months parts and labour warranty should be required.

3.2 Cold Room                                                        3 February 2016