Page 181 - 3M ELECTRICAL PRODUCTS CATALOG - 596-PAGES
P. 181

IronwoodPremium_474114_Catalog-On-Demand4.QXD  6/16/2015  11:35 PM  Page 182










                   3M™ Cold Shrink Splice Kits

                   3M™ Cold Shrink Quick Splice Low Voltage QSLV-M Series

                   3M™ Cold Shrink Quick Splice Low Voltage QSLV-M are open-ended tubular rubber sleeves with sealing mastic on each end which are factory expanded
                   and assembled onto a unique three-core system. Two cores, one on each end, are removed after the QSLV-M insulator has been centered over an inline
                   connector, allowing the ends of the tube to shrink and form a water-resistant seal. The third, center segment of the core remains inside the cold shrink
                   tube, acting as a support structure. Sizing of the cores and tube, along with the sealing mastic on each end, is designed to accommodate the variance in
                   connectors and connector crimping techniques and final dimensions without degrading the seal and insulating characteristics of the EPDM rubber tube,
                   while also making core removal easy. Two diameter sizes will cover a range of 1 kV or less cable from 8 AWG through 1000 kcmil for copper and 8 AWG
                   through 500 kcmil for aluminum conductors with crimped connectors.
                   In aerial applications where intense UV radiation will be common and visual inspection is not possible, it is recommended to overwrap the tubing with
                   Scotch® Super 33+™ Vinyl Electrical Tape or Scotch® Self-Fusing Silicone Rubber Electrical Tape 70.
                   Note: Insulator may be used on cable sizes outside of the recommended range provided both cables are within the insulation O.D. range, and the
                   connector meets the dimensional requirements shown in the table.

                                  Voltage  1000 V or less
                        Number of Conductors  Single Conductor; Multiple Conductor
                                          Low Voltage Single or Multiple
                                Cable Type
                                          Conductor Insulated Cable
                               Splice Type  Cold Shrink
                                          Insulating and protecting low voltage
                               Applications  splices in direct bury secondary low
                                          voltage applications.
                           RoHS 2011/65/EU  Yes
                           Agency Approvals  ANSI C119.1

                                                                                    Max. Connector
                   Order No.  UPC       Cable Size, Al  Cable Size, Cu  Cable Insulation O.D.  Max. Connector Length  Case Qty.
                                                                                    O.D.
                   QSLV-M(8-2/0)  051128-57236 8–2/0 AWG  8–3/0 AWG  0.20”–0.75”    0.687” (17 mm) 2.50” (63 mm)  10
                                                                 (5–19 mm)
                   QSLV-M(2-500)  051128-57237 2 AWG–500 kcmil 2 AWG–1000 kcmil 0.40”–1.60”  1.500” (38 mm) 4.25” (108 mm)  10
                                                                 (10–41 mm)






             1000 V or less









             Low Voltage Splices,


















           182                                                 FAX: 800-245-0329