5.3 - Flood Loads
Flood loads are neglected according location, type and occupancy of the building
according to SBC 1101
5.4 - Snow Loads
Snow loads are not applicable to KSA according to SBC 1101.
5.5 - Rain Loads (R)
2
Rain loads shall be permitted to ignore when assigning roof load of 2 KN/M
according the provision (3A3.3.2.1 SBC1101)
5.6 - Ice Loads
Ice loads are not applicable to KSA according to SBC 1101.
5.7 - Seismic Loads (E)
Building location: Al-Leith city–Kingdom of Saudi Arabia
Building Occupancy: Residential Villa/one family
Seismic coefficient accordance with (SBC-1101) with the following factors:
Risk Category II
Seismic Importance Factor, Ie 1.00
Soil Profile Description stiff soil
Site Classification D
The Mapped MCER acceleration parameter at short
0.150
period(Ss)
The site coefficients(Fa) 1.00
The MCER spectral response acceleration parameter
0.150
adjusted(SMS)
Design earthquake spectral response
0.1013
acceleration parameter at short period(SDS)
Seismic Design Category A
According to provision (11.1.2-SBC301) the structure is seismic design category A
if Ss<=.15g.
F= 0.01*W