-  The following superimposed loads have been considered according to

               the client and architectural design requirements:


                                                                                       load
                                          component
                                                                                       Ton/m2

                 Ceiling + Service
                 Gypsum board + Mechanical duct allowance                              0.05
                 Covering & floor fill for floor & roof

                 10 cm finishing                                                       0.20
                 20 cm finishing (Roof tiling + insulation system
                                                                                       0.320
                 + Foam Concrete)

                 Fibber tanks location                                                 1.00


               5.2 - Live Loads (L)


               Live loads consist of uniform live loads and, where required.

               Uniform live loads are assumed unit loads that are sufficient to provide for

               movable and transitory loads, such as the weight of people, furniture, portable

               equipment which may be moved over on floors.


               Special equipment live loads are based on information provided by the owner and

               by the design team, for specific areas if any, and shall be applied according to their

               sizes and shape.

               Uniform live loads for the various type of occupation are considered as follow:


                                                                                           load
                                      Occupancy or use
                                                                                          Ton/m  2


                All Floors (L)                                                             0.20




               The load from Antenna if required to be installed on slab should be provided by the
               client.