5.3 - Flood Loads
Flood loads are neglected according location, type and occupancy of the building
according to SBC 1101.
5.4 - Snow Loads
Snow loads are not applicable to KSA according to SBC 1101.
5.5 - Rain Loads (R)
2
Rain loads shall be permitted to ignore when assigning roof load of 2 KN/M
according the provision (3A3.3.2.1 SBC1101)
5.6 - Ice Loads
Ice loads are not applicable to KSA according to SBC 1101.
5.7 - Seismic Loads (E)
Building location: Al-Leith city–Kingdom of Saudi Arabia
Building Occupancy: Residential Villa/one family
Seismic coefficient accordance with (SBC-1101) with the following factors: