Page 116 - Med Plaza and Cancer Center
P. 116

"Oil-Less” Medical Air                                                             Medical Systems


               1.0 General Information (continued)



               1.3 Tankmount Standard Components

               Compressor Package
                           ®
               The LifeLine  Medical Air system is fully compliant with NFPA 99. The "oil-less" duplexed compressors are
               continuous duty rated with permanently lubricated, sealed bearings. The design is single stage, air-cooled,
               reciprocating type with corrosion resistant reed type valves with stainless steel reeds. Both the compression
               rings and rider rings are made from a long life, fluororesin material designed for continuous duty operation.
               The crankshaft is constructed of a durable nodular graphite cast iron and is fully supported on both ends by
               heavy duty ball bearings permanently lubricated and sealed. The crankcase is constructed of gray cast iron, not
               aluminum. Maximum heat dissipation is achieved through cast aluminum alloy cylinders treated for optimum
               corrosion and wear resistance. Cylinder sleeves are not required. Additionally, an insulated "heat cut" piston
               pin minimizes heat transmission from the piston wall to the piston pin needle bearing. The connecting rod is of
               a one-piece design for maximum reliability.

               Compressor Drive
               The compressors are v-belt driven through a combination compressor flywheel/sheave and steel motor sheave
               with tapered bushing protected by an OSHA approved, totally enclosed belt guard. The maximum compressor
               rotating speed does not exceed 1150 RPM.  Provisions for v-belt adjustment are provided.

               Motor
               The motor is a NEMA high efficiency type, open dripproof, 1800 RPM, with 1.15 service factor suitable for
               208/230/460V electrical service.

               Control System
               The duplex control system is NEMA 12 and U.L. Labeled. This control system provides automatic lead/lag
               sequencing with circuit breaker disconnects for each compressor with external operators, full voltage motor
               starters with overload protection, redundant 120V control circuit transformers, visual and audible reserve unit
               alarm with isolated contacts for remote alarm, hand-off-auto lighted selector switches, automatic alternation of
               both compressors with provisions for simultaneous operation if required, automatic activation of reserve if
               required, visual alarm indication for high discharge air temperature shutdown with isolated contacts for remote
               alarm, and duplexed runtime hourmeters.

               Air Receiver
               The air receiver is integrally mounted horizontally, ASME code stamped, National Board certified, and rated
               for a minimum 150 PSIG design pressure. The air receiver is equipped with a liquid level gauge glass, safety
               valve, pressure gauge, and automatic timed solenoid drain valve. The duplexed compressor/motor subbases are
               fully isolated from the air receiver and from the steel support structure by means of a four-point heavy-duty
               spring isolation system for a minimum of 95% isolation efficiency.

               Intake Piping
               Each compressor has a piped intake with one "hospital type" inlet air filter with threaded opening for remote
               intake connection.













                                                             1-5
   111   112   113   114   115   116   117   118   119   120   121