Page 133 - Med Plaza and Cancer Center
P. 133
"Oil-Less” Medical Air Medical Systems
4.0 Troubleshooting
Problem Possible Cause Solution
Wrong direction of rotation Motor wired incorrectly Switch motor leads
Low discharge pressure System piping leaks Repair leaks
Defective pressure gauge Replace gauge
Pressure switch open Adjust or replace
No power to solenoid Check electrical connections
Belts slipping Adjust tension
Intake filter clogged Clean or replace
Gasket leaks; piston ring wear Replace gaskets and rings
Compressor cycles too often System undersized Contact BeaconMedæs
Incorrect pressure setting Adjust pressure switch
Faulty pressure switch Replace switch
System piping leaks Repair leaks
Check valve or line to receiver Replace if necessary
is leaking or plugged
Both dryers on line Valve off one dryer
Water in air receiver Drain air receiver
Compressor won’t shut off Pressure switch out Adjust or replace
of adjustment or faulty
Excessive belt wear Belt tension Adjust tension
Belt alignment Realign compressor &
motor sheaves
Abnormal noise Mounting bolts loose Tighten bolts
Belt tension Adjust tension
Worn piston or rider ring; Replace
broken valve parts
Note: For air dryer troubleshooting, see Appendix A.
4-2