Page 134 - Med Plaza and Cancer Center
P. 134
"Oil-Less” Medical Air Medical Systems
5.0 Maintenance
5.1 Maintenance Schedule
WARNING:
BEFORE STARTING ANY MAINTENANCE PROCEDURES, DISCONNECT ALL POWER
TO THE PACKAGE.
Release all pressure from the package before removing, loosening, or servicing any covers, guards,
fittings, connections, or other devices.
Never perform any maintenance functions while the unit is in operation.
Item Frequency Action
Check condensate in tank Daily Open manual drain valve: check
auto drain
Check operation of safety valve Weekly Manually release pressure
Check inlet air filter(s) Weekly Inspect and clean or replace
Check nuts, bolts, fittings, etc. Monthly Inspect and tighten
Crankcase filter(s) Monthly Inspect and clean or replace
Check belt tension Monthly Inspect and tighten or replace
Inspect
Check compressor piston rings & rider rings Every 3,000 hours
Check compressor valve plates and valve parts Every 12,000 hours Inspect and repair or replace
1 - 20 HP
Piston rings and rider rings
1 - 7.5 HP Every 10,000 hours Replace
10 - 20 HP Every 8,000 hours
Ball and needle bearings
1 - 7.5 HP Every 10,000 hours Replace
10 - 20 HP Every 8,000 hours
Check flow through orifice of dew point sensor Every 6 months Check for flow blockage
Check dew point sensor accuracy Every 12 months Verify dew point sensor accuracy
(contact BeaconMedæs)
Calibrate CO monitor Every 6 months See Appendix B
Replace pre-filters & afterfilters Yearly Replace filter elements
Replace Dryer Desiccant 5 years See Appendix A
5-1