P. 243
Medical Lubricated Vacuum
2.0 Installation
WARNING:
THE VACUUM EXHAUST VENT MUST BE
LOCATED AWAY FROM MEDICAL AIR
INTAKES, DOORS, AND OPENINGS IN
THE BUILDINGS TO MINIMIZE POSSIBLE
CONTAMINATION TO THE FACILITY, IN
ACCORDANCE WITH NFPA 99.
Table 2.2 Exhaust Pipe Length
System Exhaust Pipe Length (ft) - See Notes
LifeLine Pump
Units Connection 25 50 75 100 150 200 250 300 350 400 450 500
1.5 Hp 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25
2 Hp 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.5 1.5 1.5
3 Hp 1.25 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2
5 Hp1 1.25 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 2
SIMPLEX 5 Hp2 2 2 2 2 2 2 2 2 2 2 3 3 3
2
2
2
3
3
2
3
3
3
2
3
2
2
7.5 Hp
10 Hp 2 2 2 2 3 3 3 3 3 3 3 3 3
15 Hp 3 3 3 3 3 3 3 3 3 4 4 4 4
20 Hp 3 3 3 3 3 3 3 3 4 4 4 4 4
25 Hp 3 3 3 3 3 3 4 4 4 4 4 4 4
1.5 Hp 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.5 1.5 1.5 1.5 1.5 1.5
2 Hp 1.25 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2
3 Hp 1.25 1.5 1.5 1.5 1.5 2 2 2 2 2 2 3 3
5 Hp1 1.25 2 2 2 2 2 3 3 3 3 3 3 3
DUPLEX 5 Hp2 2 2 2 2 3 3 3 3 3 3 3 3 3
3
3
3
3
3
3
3
4
7.5 Hp
4
2
3
3
3
10 Hp 2 3 3 3 3 3 4 4 4 4 4 4 4
15 Hp 3 3 3 4 4 4 4 4 4 4 4 4 5
20 Hp 3 4 4 4 4 4 4 4 5 5 5 5 5
25 Hp 3 4 4 4 4 4 5 5 5 5 5 5 5
5 Hp2 2 3 3 3 3 3 3 3 3 4 4 4 4
7.5 Hp 2 3 3 3 3 3 4 4 4 4 4 4 4
TRIPLEX 10 Hp 2 4 4 4 4 4 4 4 4 4 5 5 5
5
5
5
5
5
4
4
15 Hp
3
4
5
5
4
4
20 Hp 3 5 5 5 5 5 5 5 5 5 6 6 6
25 Hp 3 5 5 5 5 5 5 6 6 6 6 6 6
4107 9000 96.03 2-4