Medical Lubricated Vacuum
3A.0 Start Up - TotalAlert Embedded Controls
CAUTION: Vibration during shipment and Check all voltages supplied to the LifeLine® system
installation can loosen electrical terminals, fuse to ensure they are the required value and phases
inserts, and mechanical connections. Tighten as needed by the control panel.
necessary.
Apply power to the system and turn the disconnect
• Check the electrical cabinet for any broken switches to “On”.
components.
• Check that all motor starter connections are
tight and that there are no loose objects such
as terminal lugs, screws, nuts, etc., in the
cabinet.
3A.2 Initial Start-up
CAUTION: Complete the prestart-up procedure
before continuing with the initial start-up
procedure
WARNING:
To prevent electrical shock, ensure that
ALL electrical power to the system is OFF, Manual Override
including the disconnect switches. The Switch
facility’s supply circuit breaker should O - On Manual
also be locked out.
X - Off
A - Automatic
3A.2.1 Lubrication Figure 3A.1 Unit PCB Override Switch
The pumps are oil lubricated. The lubricating Prior to actual operation, the pumps must be
oil can be put into the pump at the oil fi ller port checked for correct rotation.
of the oil separator housing, observing the “MAX”
and “MIN” position at the oil level sight glass. (For Inside the control cabinet, switch one of the unit
recommended oil type, refer to Section 6.1.) After printed circuit boards from the manual override
fi lling, make sure the oil fi ller port is closed. “Off ” position to the bottom position, the default
“Automatic” mode. Make sure the Pump Mode on
All LifeLine® lubricated vacuum pumps are shipped the Unit touchscreens are in the Off position, see
with the required amount of oil for start-up. The Figures 3.2 and 3.3. (See Figure A.15 for complete
systems are shipped with separate oil containers, list of Screen Toolbar Descriptions).
which must be added before start-up.
Check for correct direction of rotation of each pump
3A.2.2 Pump Rotation by pressing the “Rotation” button on touchscreen
display (found in the Service section of the Unit
Inside the control panel, make sure that all unit touchscreens) and observing rotation. See Figure
printed circuit boards are set to the manual 3.4. The Pump Mode for each compressor must
override “Off ” position. This is indicated by the be in the Off Position for the Rotation to function.
middle position “X” on the three-position sliding
switch as shown in Figure 3.1.