Medical Lubricated Vacuum
3B.0 Start Up - Basic Controls
CAUTION: Vibration during shipment and Check all voltages supplied to the LifeLine® system
installation can loosen electrical terminals, fuse to ensure they are the required value and phases
inserts, and mechanical connections. Tighten as needed by the control panel.
necessary.
Using the Hand-Off -Auto switch on the door of the
• Check the electrical cabinet for any broken control panel, jog the motor of the specifi c pump
components. that is to be checked by momentarily turning the
switch to “Hand” and back to “Off ”. By observing
• Check that all motor starter connections are the cooling fan of the motor, you can determine
tight and that there are no loose objects such the rotation of the pump. Pump rotation should
as terminal lugs, screws, nuts, etc., in the be counterclockwise when looking at the rear of
cabinet. the motor. Directional arrows are located on each
pump.
3B.2 Initial Start-up
If the pumps are rotating in the wrong direction,
CAUTION: Complete the prestart-up procedure rotation can be reversed by switching any two
before continuing with the initial start-up main power leads to the panel. Correct rotation
procedure should be confi rmed in the previous manner.
WARNING: WARNING:
To prevent electrical shock, ensure that Do not allow the vacuum pump to
ALL electrical power to the system is OFF, run backwards.
including the disconnect switches. The
facility’s supply circuit breaker should
also be locked out. Repeat the process of testing rotation for each
vacuum pump.
3B.2.1 Lubrication 3B.3 Initial Operation
The pumps are oil lubricated. The lubricating Using the “Hand-Off -Auto” switch, start pump by
oil can be put into the pump at the oil fi ller port switching to “Auto”.
of the oil separator housing, observing the “MAX”
and “MIN” position at the oil level sight glass. (For Run the pump for two minutes in the correct
recommended oil type, refer to Section 6.1.) After rotation. Stop the pump and top off the oil level
fi lling, make sure the oil fi ller port is closed. utilizing the oil fi ller port to the correct level as
shown in the sight glass. DO NOT OPEN THE
All LifeLine® lubricated vacuum pumps are shipped FILLER PORT WHILE THE PUMP IS RUNNING.
with the required amount of oil for start-up. The
systems are shipped with separate oil containers, WARNING:
which must be added before start-up.
Pumps that have reached operating
3B.2.2 Pump Rotation temperature may have a high surface
temperature on the top of the exhaust
Prior to actual operation, the pumps must be muffl er.
checked for correct rotation.
DO NOT TOUCH!
Apply power to the system and turn the disconnect
switches to “On”.
4107 9000 96.03 3B-2