Page 254 - Med Plaza and Cancer Center
P. 254

Medical Lubricated Vacuum


            4A.0  General Operation - TotalAlert Embedded Controls



            Note:  This section applicable to Lubricated Rotary   reset once the system reaches its normal operating
            Vane Medical Vacuum Systems with the TotalAlert      vacuum and the lag pump times out and stops.
            Embedded electronic control system.                  See Figure 4A.1.


                               WARNING:
             NEVER      RUN    THE     PUMP     WITHOUT
             LUBRICATING OIL!


            4A.1  Electrical Control Panel


            The LifeLine multiplex control system is U.L.
            labeled. The control system has a touch screen
            control, automatic lead/lag sequencing, external
            operators with circuit breaker disconnects, full
            voltage motor starters, overload protection, 24V
            control circuit, and automatic-off -manual selector
            for each vacuum pump. Automatic alternation
            of all vacuum pumps is based on fi rst-on/fi rst-
            off  principle with provisions for simultaneous                                  Reset Button
            operation if required. Automatic activation of       Figure 4A.1 Main Screen - Reset Button
            reserve unit, if required, will activate an audible
            alarm as well as a visual alarm on the control panel.    In a typical duplex system, one pump will be able
            The control panel displays service alert, run hours   to handle the system load. The control system will
            for each vacuum pump, system status, system          signal the lead pump to start when the vacuum
            vacuum level, and high discharge air temperature.    transducer senses the vacuum level below its set
            A complete alarm and service history is available    point. If one pump can carry the load, then the
            on the control panel. (see Appendix A for more       vacuum level will rise and maintain the vacuum
            details)                                             level setting.  At this point, if the minimum run
                                                                 timer for that pump has been satisfi ed, the control
            During normal operation, all pumps should be         system will turn off  the lead pump.  If the minimum
            in the “Automatic” position so that the control      run timer for that pump has not been satisfi ed, the
            system can eff ectively run the system.  The control   lead pump will continue to run until the timer
            system monitors the system vacuum level, starts      expires. When the system vacuum drops below
            and stops the pumps depending on changing            the vacuum level setting, the control system will
            vacuum level conditions and minimum run time         automatically sequence the lead role to the other
            values, and automatically alternates the lead        pump and will start it. This is also known as “fi rst
            position between units.                              on/fi rst off ” instead of the more traditional “last
                                                                 on/fi rst off ”.
            On the initial system start-up, when the system
            vacuum level is below the set point of the vacuum
            transducer, pump 1 will start immediately. Another
            pump starts after a programmed time delay.  The
            time delay prevents high inrush current after a
            power failure or emergency power switch over.
            During this initial system start-up, the lag alarm
            may come on at this point and is normal.  It can be

                                                             4A-1                                 4107 9000 96.03
   249   250   251   252   253   254   255   256   257   258   259