Medical Lubricated Vacuum
3A.0 Start Up - TotalAlert Embedded Controls
3A.3 Initial Operation
Start each pump by pressing “Automatic” on the
touchscreen. See Figure 3.5.
Figure 3A.5 Unit Screen - Automatic Mode
WARNING:
Pumps that have reached operating
temperature may have a high surface
temperature on the top of the exhaust
muffl er.
DO NOT TOUCH!
Run the pump for two minutes in the correct
rotation. Stop the pump and top off the oil level
utilizing the oil fi ller port to the correct level as
shown in the sight glass. DO NOT OPEN THE
FILLER PORT WHILE THE PUMP IS RUNNING.
After testing each pump, if everything appears
normal, put each pump into the “Automatic”
mode and allow each pump to run until vacuum
builds. Check for any leaks in the piping. Repair
leaks, if needed.