ERROR CODE MESSAGES ON THE MANIFOLD DISPLAY
SYMPTOM CAUSE CORRECTIVE ACTION
E01 Sensor not connected Check sensor wiring. Reconnect wire
properly.
E06 Sensor wires between the manifold Reverse polarity or replace defective
module, shorted out on reversed wire.
polarity.
E10 Shuttle valve shaft hung up or not Under Low Flow conditions, E10 could
shuttled-fully. Operating regulators happen during switchover. This is
not set up properly, limit switch normal under this Low Flow condition.
wiring connector. When the shuttle has fully shuttled over
the E10 error will clear.
Reset operating regulators to specified
setting, make sure connections are
properly connected to switches.