        ERROR CODE MESSAGES ON THE MANIFOLD DISPLAY


                     SYMPTOM                              CAUSE                        CORRECTIVE ACTION


          E01                                Sensor not connected              Check sensor wiring. Reconnect wire
                                                                               properly.

          E06                                Sensor wires between the manifold  Reverse polarity or replace defective
                                             module, shorted out on reversed   wire.
                                             polarity.

          E10                                Shuttle valve shaft hung up or not   Under Low Flow conditions, E10 could
                                             shuttled-fully. Operating regulators  happen during switchover. This is
                                             not set up properly, limit switch   normal under this Low Flow condition.
                                             wiring connector.                 When the shuttle has fully shuttled over
                                                                               the E10 error will clear.

                                                                               Reset operating regulators to specified
                                                                               setting, make sure connections are
                                                                               properly connected to switches.