                          Symptom                    Possible Cause                 Corrective Action

                16)High alarm with -- FF 33 -- display  Pressure or vacuum signal  a. Correct sensor wiring.
                   on digital display module.    to digital display module out b. If alarm panel contains another
                                                 of measurement range (too      working digital display module,
                                                 high) as a result of:          remove field wiring connector from
                                                 a. Shorted sensor wiring.      suspect module and connect to
                                                 b. Faulty digital display module.  working (test) module.  If test
                                                 c. Faulty sensor module.       module provides any reading other
                                                 d. Digital display module      than
                                                   gas/vacuum service           - - FF 33 --, replace faulty digital display
                                                   programmed to NN OO NN EE with  module.
                                                   digital sensor connected.  c. If test module in step b above also
                                                                                gives -- FF 33 --, replace faulty sensor
                                                                                module.
                                                                              d. Program digital display module for
                                                                                the correct gas/vacuum service.
                                                                                Refer to Set-Up instructions page
                                                                                36.

                17)High and low alarm with       Gas/vacuum service           a. Correct sensor wiring.
                   - - FF 44 -- display on digital display  mismatch between digital  b. Program digital display module for
                   module.                       display module and digital     the correct gas/vacuum service.
                                                 sensor module as a result      Refer to Set-Up instructions page
                                                 of:                            36.
                                                 a. Sensor wired to wrong digital
                                                   display module.
                                                 b. Digital display module
                                                   programmed with the wrong
                                                   service.
                18)No blinking LED on digital    No power to digital sensor   a. Correct sensor wiring.
                   sensor module.                due to:                      b. Replace digital sensor module.
                                                 a. Faulty wiring.
                                                 b. Faulty digital sensor module.
                19)Fast blinking LED on digital  Sensor out of range:         a. Verify piping connections.  Vacuum
                   sensor module.                a. Vacuum digital sensor       sensor maximum overpressure: 30
                                                   module connected to          psi.
                                                   pressure service.          b. Verify piping connections.
                                                 b. Pressure digital sensor   c. Replace digital sensor module.
                                                   module connected to
                                                   vacuum service.
                                                 c. Faulty digital sensor module.