Page 570 - Med Plaza and Cancer Center
P. 570

Troubleshooting Guide



                         Symptom                     Possible Cause                 Corrective Action
                1) No visual indicators illuminated a. AC power is not turned on.  a. Check AC power source.
                  on entire alarm panel        b. Blown internal fuse.        b. Replace fuse.
                                               c. AC power wiring is not      c. Check AC entrance wiring at power
                                                  connected.                    supply terminals.  Verify two-pin
                                               d. Three-wire power supply       plastic connector is plugged into
                                                  harness is not connected      power supply circuit board.
                                                  between power supply and    d. Check connections on each end
                                                  annunciator board             including orientation of cable
                                               e. Faulty power supply           connectors.  Reconnect if
                                                  assembly.                     necessary.
                                                                              e. Replace power supply assembly.


                2) No visual indicators illuminated a. 20-wire ribbon cable(s)  a. Reconnect ribbon cable(s).
                  on isolated module(s). Green    between annunciator module  b. All alarm panels have two 20-wire
                  annunciator module POWER        and digital display or multi-  ribbon cables (attached to
                  indicator is illuminated.       signal modules not            annunciator connectors “J1” and
                                                  connected.                    “J2”).  Remove suspect cable (both
                                               b. Faulty 20-wire ribbon cable.  ends) and replace with other cable.
                                               c. Faulty digital display or multi-  If problem is corrected, replace
                                                  signal module.                faulty cable.
                                               d. Faulty annunciator module.  c. If alarm panel contains another
                                                                                working digital display or multi-
                                                                                signal module, unplug ribbon cable
                                                                                from working module and connect
                                                                                to non-working module.  If module
                                                                                does not illuminate, replace faulty
                                                                                digital display or multi-signal
                                                                                module.
                                                                              d. Replace faulty annunciator module.


                3) Constant audible alarm that  a. Faulty digital display or multi-  a. Disconnect digital display and/or
                  can not be silenced by          signal module.                multi-signal modules one at a time
                                               b. Faulty 20-wire ribbon cable.  from 20-wire ribbon cables.  If
                  pressing front panel MUTE
                  button. No visual alarm on any  c. Faulty annunciator module.  disconnecting a module cancels
                                                                                audible alarm, replace that faulty
                  digital display or multi-signal
                                                                                module.
                  module.
                                                                              b. After all modules have been
                                                                                disconnected from 20-wire ribbon
                                                                                cables, disconnect each cable, one
                                                                                at a time from annunciator module.
                                                                                If disconnecting ribbon cable
                                                                                cancels alarm, replace that faulty
                                                                                cable.
                                                                              c. If both 20-wire ribbon cables have
                                                                                been removed from annunciator
                                                                                module, and audible alarm has not
                                                                                cancelled, replace faulty
                                                                                annunciator module.



                                                                                                                 45
                                                                                            Part No. 6-847684-00 Rev. E00