Page 567 - Med Plaza and Cancer Center
P. 567
Testing
Multi-Signal Module:
Press and hold front panel TEST button for
five seconds to initiate following sequence:.
• Audible alarm sounds briefly.
• All red and green indictors flash for five
seconds. Bit 4 (green)
• Software revision is displayed as Bit 5 (green)
follows: SIGNAL 1
- Expressed as a three digit number Bit 6 (green)
SIGNAL 2
(e.g. 1.0.2). Bit 7 (green)
- Each digit of number is displayed SIGNAL 3
Bit 0 (red)
separately for two seconds and SIGNAL 4
separated from the next digit by a Bit 1 (red) SIGNAL 5
brief flashing of all indicators.
Bit 2 (red)
- Each number is displayed in a
binary code where each multi-signal Bit 3 (red)
module indicator has a binary value.
- Example: Software revision 1.0.2
would be displayed as follows:
• First digit is determined by two
second illumination of top left Binary data represented by LED indicators
indicator (bit 0 = number 1). Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
• All indicators quickly flash.
• Second digit is determined to be 128 64 32 16 8 4 2 1
0 because no indicators are Numeric value of each bit
illuminated for two seconds.
• All indicators quickly flash.
• Third digit of is determined by
two second illumination of
second left indicator (bit 1 =
number 2).
• After all three digits of software revision
have been displayed, all indicators
illuminate for one second before
displaying current MEGA network
address.
• Current network address is displayed
for two seconds in a binary code where
each multi-signal module indicator has
a binary value.
• All indicators illuminate for one second
and module returns to monitoring
mode.
42
Part No. 6-847684-00 Rev. E00