“Oil-Less” Scroll Medical Air
Appendix D: TotalAlert Embedded Control System
1. Click System Trend Setup to access the System
Trend Setup page.
2. Select a time interval from the pull-down list
of options.
3. Click the Submit button.
D.7.10 Electronic Notifi cation Setup
Figure D.34 Website Setup This Electronic Notifi cation Setup page (Figure
D.36) is used to confi gure the Electronic Notifi cation
1. Click Website Setup to access the Website feature of the TotalAlert Embedded control
Setup page.
system. By setting up the Electronic Notifi cation,
key personnel can receive notifi cations of all alarm/
2. Select a time interval from the pull-down list shutdown alerts and/or all maintenance alerts
of options.
(e-mail, pager, phone text message). The device
acts as an SMTP client. An SMTP server is required
3. Click the Submit button.
for electronic notifi cation to function.
D.7.9 System Trend Setup
Figure D.35 System Trend Setup
This System Trend Setup page (Figure D.35) is
used to confi gure the trend log for the website and Figure D.36 Electronic Notifi cation Setup
to allow the data to be cleared. The System Trend
screen contains a maximum of 720 events for each 1. Click Electronic Notifi cation Setup to access
of the items recorded, so the actual duration of the the Electronic Notifi cation Setup page.
trend log changes with the time interval selected.
The durations available to select are 6 hours, 24 2. Select Enable to enable the e-mail notifi cation
hours, 2.5 days, and 10 days. tool.
3. Enter up to fi ve email addresses.