Page 272 - Womens Pavilion
P. 272
Oil-Less Claw Medical Vacuum
2.0 Installation
2.1 Inspection Upon Receiving Place units to ensure high visibility of indicators
and gauges and for performing maintenance on the
The condition of the LifeLine® Claw Medical system. Refer to your installation diagram. If you
Vacuum System should be carefully inspected do not have one, please contact BeaconMedæs
upon delivery. Any indication of damage by the Technical Support at 888-4-MEDGAS.
carrier should be noted on the delivery receipt,
especially if the system will not be immediately 2.3 Location
uncrated and installed. BeaconMedæs ships all
systems F.O.B. factory; therefore, damage is the The LifeLine® Claw Medical Vacuum system should
responsibility of the carrier, and all claims must be be installed indoors in a clean, well-ventilated
made with them. Claw systems may remain in their environment. Areas of excessive dust, dirt or other
shipping containers until ready for installation. If air-borne particulate should be avoided.
LifeLine® Claw systems are to be stored prior to
installation, they must be protected from the Certain considerations should be given to the
elements to prevent rust and deterioration. placement of the system. The package may be
installed in a location that is fl at, level, and will
DO NOT REMOVE the protective covers from the support its weight. Clearance between the unit
inlet and discharge connection ports of the unit and adjacent walls should be no less than 24”
until they are ready for connecting to the hospital’s to ensure suffi cient airfl ow for cooling. There
pipeline distribution system. should be a minimum of three feet of clearance
in front of the control panel for safe operation
2.2 Handling and maintenance. A vertical distance of 24” is
required above the modules for ventilation and
maintenance.
WARNING:
USE APPROPRIATE LOAD RATED LIFTING No special foundation is required. However, all
EQUIPMENT AND OBSERVE SAFE LIFTING units must be securely bolted using all mounting
PROCEDURES DURING ALL MOVES. holes provided. If a raised concrete pad is used,
the module bases must not overhang the concrete
base. A method to drain away moisture is
The vacuum package can be moved with either a necessary.
forklift or dollies. Keep all packing in place during
installation to minimize damage. Walk along the Adequate ventilation is required. The pumps are
route the unit must travel and note dimensions air-cooled. Therefore, it is very important that the
of doorways and low ceilings. LifeLine® Claw ambient temperature should be between 40˚F
systems are designed to go through 36” doorways. and 105˚F (if the maximum ambient exceeds
105˚F, contact factory for special instructions).
Most Single Point Connection systems can be The system should be located as close as possible
separated to fi t through 36” doorways (Pentaplex to the point of usage to prevent excessive loss of
and Hexaplex control skid bases measure 40.5”). operating vacuum due to pressure drop.
If separating bases, carefully label all removed
electrical connections for easier re-assembly at the When selecting the location for the system,
fi nal destination. remember to keep in mind the requirements for
service, such as cleaning, changing fi lters, and
changing oil.
2-1 4107 9000 95.04