TotalAlert Infinity NFPA Medical Gas Notification System
                                  ™


              *Table 1: Gas Sensor Module Options                           **Table 2: I/O Boards


              Part Number          Gas Sensor Assembly            MEGA3™           I/O Boards       Description
           4107 2131 00        O2 Sensor Assembly                  Alarms
           4107 2131 01        N2O Sensor Assembly              4107 2130 10 B10 (Signal Input     20 Inputs
           4107 2131 02        MedAir Sensor Assembly                         Board)
           4107 2131 03        Vac Sensor Assembly              4107 2130 11 B11 (Signal Input     20 Inputs
                                                                              Board)
           4107 2131 04        N2 Sensor Assembly
                                                                4107 2130 12 B12 (Signal Input     20 Inputs
           4107 2131 05        IAIR Sensor Assembly                           Board)
           4107 2131 06        WAGD Sensor Assembly             4107 2130 40 B40 (Relay Board)     16 Relay
           4107 2131 07        CO2 Sensor Assembly                                                 Outputs
           4107 2131 08        CO2-O2 Sensor Assembly           4107 2130 41 B41 (Relay Board)     16 Relay
                                                                                                   Outputs
           4107 2131 09        O2-CO2 Sensor Assembly
           4107 2131 10        HE-O2 Sensor Assembly            4107 2130 42 B42 (Relay Board)     16 Relay
                                                                                                   Outputs
           4107 2131 11        O2-HE Sensor Assembly            4107 2130 43 B43 (Relay Board)     16 Relay
           4107 2131 12        HE Sensor Assembly                                                  Outputs
           4107 2131 13        LAB-AIR Sensor Assembly          4107 2130 50 B50 (4-20mA           4 Inputs for
           4107 2131 14        LAB-VAC Sensor Assembly                        Combination Board) 4-20mA Signals
           4107 2131 15        O2-100 Sensor Assembly           4107 2130 60 B60 (Gas Input        8 Gases
           4107 2131 16        MedAir-100 Sensor Assembly                     Board)
                                                                4107 2130 65 B65                   3 Gases, 7
           4107 2131 17        CO2-100 Sensor Assembly
                                                                              (Gas Combination     Inputs, 6 Relay
           4107 2131 18        AR Sensor Assembly                             Board)               Outputs
           4107 2131 19        AGSS Sensor Assembly            Periodic Maintenance:
           4107 2131 20        O2-N2O Sensor Assembly
                                                               Inspect the alarm periodically and perform
           Cleaning:                                           a self test (see Section 4.1.7 - Information
           Use clean dry microfiber cloth or soft lint-        Screen). This ensures proper operation of the
           free cloth to remove any smudges located on         alarm. Any damaged components inside the
           the touchscreen. Make sure not to apply too         alarm should be replaced by an authorized
           much pressure on the screen when cleaning           BeaconMedæs service technician.
           it. Never use paper towels or tissue paper          For TotalAlert Infinity  alarms, the coin cell
                                                                                      ™
           which contain wood fibers that will scratch         battery on the Advanced Module needs to
           any plastic surface.                                be replaced every 5 years.  Replace with CR-
                                                               2032 coin cell battery.
                                                                       Coin Cell
                                                                       Battery














                                                                  Figure 231: Coin Cell Battery Maintenance
           4107 9016 58.02                                  6-2