TotalAlert Infinity NFPA Medical Gas Notification System
™
Troubleshooting (continued)
Symptom Possible Cause Corrective Action
Area Display pressure/ Bad gauge on pipeline Verify gauge used on pipeline
vacuum reading not Incorrect unit of measure Check unit of measure, if incorrect, repro-
matching pipeline. gram unit of measure.
Gas sensor out of calibration Adjust Zero Offset to correct reading.
(Note: there is a max of 3 psi / 3 “hg offset
adjustment). If sensor cannot be adjusted
enough, replace sensor.
High or Low alarm, with Alarm set points have been changed. Verify / correct alarm set points.
normal pressure display-
ing on Area display
Screen is blank, power on Screen backlight will time out and If screen does not awaken when approach-
LED is illuminated shut off. Motion sensor will awaken ing alarm, touch screen to awaken. Possible
screen when motion is sensed within bad motion sensor.
5 ft of screen.
Audible alarm reactivates A new alarm condition has occurred. If alarm condition previously silenced,
a short period of time self corrects and then reactivates again,
after Silence button has the alarm panel treats this as a new alarm
been pressed condition.