Page 151 - 2018_IFC
P. 151

FIRE PROTECTION AND LIFE SAFETY SYSTEMS



         905.4 Location of Class I standpipe hose connections.     not located  within an  interior exit  stairway are  not
         Class I standpipe hose connections shall be provided in all of  required to be enclosed  within fire-resistance-rated
         the following locations:                                  construction.
           1. In every required interior exit stairway, a hose connec-  905.4.2 Interconnection. In buildings  where more  than
              tion shall be provided for each story above and below  one standpipe is provided, the standpipes shall be inter-
              grade plane. Hose connections shall be located at the  connected in accordance with NFPA 14.
              main floor landing unless otherwise  approved by  the  905.5 Location of  Class  II  standpipe hose connections.
              fire code official.                             Class II standpipe hose connections shall be located so that
                Exception: A single hose connection shall be per-  all portions of the building are within 30 feet (9144 mm) of a
                mitted to be installed in the open corridor or open  nozzle attached to 100 feet (30 480 mm) of hose. Class II
                breezeway between open stairs that are not greater  standpipe hose connections shall be located where they will
                than 75 feet (22 860 mm) apart.               have ready access.
           2. On each side of the wall adjacent to the exit opening of  905.5.1 Groups A-1 and  A-2.  In  Group A-1 and A-2
              a horizontal exit.                                 occupancies with occupant loads of more than 1,000, hose
                Exception: Where floor areas adjacent to a horizon-  connections shall be located on each side of any stage, on
                tal exit are reachable from an interior exit stairway  each side of the rear of the auditorium, on each side of the
                hose connection by a 30-foot (9144 mm) hose      balcony and on each tier of dressing rooms.
                stream from a nozzle attached to 100 feet (30 480  905.5.2 Protection. Fire-resistance-rated protection of ris-
                mm) of hose, a hose connection shall not be required  ers and laterals of Class II standpipe systems is not
                at the horizontal exit.                          required.
           3. In every exit passageway, at the entrance from the exit  905.5.3 Class II system 1-inch hose. A minimum 1-inch
              passageway to other areas of a building.           (25 mm) hose shall be allowed to be used for hose stations
                Exception: Where floor areas adjacent to an  exit  in light-hazard occupancies where investigated and listed
                passageway are reachable from an interior exit stair-  for this service and where approved by the fire code offi-
                way hose connection by a 30-foot (9144 mm) hose  cial.
                stream from a nozzle attached to 100 feet (30 480  905.6  Location of Class III standpipe hose connections.
                mm) of hose, a hose connection shall not be required  Class III standpipe systems shall  have hose connections
                at the entrance  from the  exit passageway to  other  located as required for Class I standpipes in Section 905.4
                areas of the building.                        and shall have Class II hose connections as required in Sec-
           4. In covered mall  buildings,  adjacent  to each exterior  tion 905.5.
              public entrance to the  mall and adjacent to each  905.6.1 Protection. Risers and laterals of Class III stand-
              entrance from an exit passageway or exit corridor to the  pipe systems shall be protected as required for Class I sys-
              mall.  In open mall buildings, adjacent to each public  tems in accordance with Section 905.4.1.
              entrance to the mall at the perimeter line and adjacent  905.6.2 Interconnection. In buildings  where more  than
              to each entrance from an exit passageway or exit corri-  one Class III standpipe is provided, the standpipes shall be
              dor to the mall.                                   interconnected in accordance with NFPA 14.
           5. Where the roof has a slope less than four units vertical  905.7 Cabinets. Cabinets containing fire-fighting equipment,
              in 12 units horizontal (33.3-percent slope), a hose con-  such as standpipes, fire hose, fire extinguishers or fire depart-
              nection shall be located to serve the roof or at the high-  ment valves, shall not be blocked from use or obscured from
              est landing of an interior exit stairway with access to  view.
              the roof provided in accordance with Section 1011.12.
                                                                 905.7.1 Cabinet equipment identification. Cabinets shall
           6. Where the most remote portion  of a nonsprinklered  be identified  in an  approved manner  by a  permanently
              floor or story is more than 150 feet (45 720 mm) from a
                                                                 attached sign with letters not less than 2 inches (51 mm)
              hose connection or the most remote portion of a sprin-  high in a color that contrasts with the background color,
              klered floor or story is more than 200 feet (60 960 mm)  indicating the equipment contained therein.
              from a hose connection, the fire code official is autho-
                                                                   Exceptions:
              rized to require that additional hose connections be pro-
              vided in approved locations.                           1. Doors not large enough to accommodate a writ-
                                                                        ten sign shall be marked with a permanently
           905.4.1 Protection. Risers and laterals of Class I stand-
                                                                        attached pictogram  of  the equipment contained
           pipe systems not located within an interior exit stairway
           shall be protected by a degree of fire resistance equal to   therein.
           that required for  vertical enclosures in  the  building in  2. Doors that have either an approved visual identi-
           which they are located.                                      fication clear glass panel or a complete glass door
                                                                        panel are not required to be marked.
              Exception: In buildings equipped throughout with an
              approved automatic sprinkler system, laterals that are