FIRE PROTECTION AND LIFE SAFETY SYSTEMS



                  7. Trim  valves to pressure switches  in dry,  preaction  sprinkler systems of Section 903 shall be approved by the fire
                    and deluge sprinkler systems that are sealed or  code official.
                    locked in the open position.                     904.2.1 Restriction on using automatic sprinkler sys-
               903.4.1 Monitoring. Alarm, supervisory and trouble sig-  tem exceptions or reductions. Automatic fire-extinguish-
               nals shall be distinctly different and shall be automatically  ing systems shall not be considered alternatives for the
               transmitted to an approved supervising station or, where  purposes  of exceptions or  reductions allowed for  auto-
               approved by the fire code official, shall sound an audible  matic sprinkler systems or by other requirements of this
               signal at a constantly attended location.             code.
                  Exceptions:                                        904.2.2 Commercial hood  and duct systems. Each
                                                                     required commercial kitchen exhaust hood and duct sys-
                    1. Underground key or hub valves in roadway boxes
                       provided by the municipality or public utility are  tem required by Section 607 to have a Type I hood shall be
                       not required to be monitored.                 protected with an  approved automatic fire-extinguishing
                                                                     system installed in accordance with this code.
                    2. Backflow prevention device test valves located in  904.3 Installation. Automatic  fire-extinguishing systems
                       limited area sprinkler system supply piping shall  shall be installed in accordance with this section.
                       be locked  in the open  position. In occupancies
                       required to be equipped with a fire alarm system,  904.3.1 Electrical  wiring. Electrical  wiring  shall be in
                       the  backflow preventer  valves shall be electri-  accordance with NFPA 70.
                       cally supervised by a tamper switch installed in  904.3.2 Actuation. Automatic fire-extinguishing systems
                       accordance with NFPA 72 and separately annun-  shall be automatically actuated and provided with a man-
                       ciated.                                       ual means of actuation in accordance with  Section
               903.4.2 Alarms. An approved audible device, located on  904.12.1. Where more than one hazard could be simulta-
               the exterior of the building in an approved location, shall  neously involved in fire due to their proximity, all hazards
               be connected to each  automatic sprinkler system. Such  shall be protected by a single system designed to protect
               sprinkler  waterflow alarm devices shall be activated  by  all hazards that could become involved.
               water flow equivalent to the flow of a single sprinkler of  Exception: Multiple systems shall be permitted to be
               the smallest orifice size installed in the system. Where a  installed if they are designed to operate simultaneously.
               fire alarm system is installed, actuation of the automatic  904.3.3 System interlocking. Automatic equipment inter-
               sprinkler system shall actuate the building fire alarm sys-
                                                                     locks with fuel shutoffs, ventilation controls, door closers,
               tem.                                                  window shutters, conveyor openings, smoke and heat
               903.4.3 Floor control valves. Approved supervised indi-  vents and other features necessary for proper operation of
               cating control valves shall be provided at the point of con-  the fire-extinguishing system shall be provided as required
               nection to the riser on each floor in high-rise buildings.  by the design and installation standard utilized for the haz-
                                                                     ard.
             903.5 Testing and maintenance. Sprinkler systems shall be
             tested and maintained in accordance with Section 901.   904.3.4 Alarms  and warning signs.  Where alarms are
                                                                     required to indicate the operation of automatic fire-extin-
             903.6 Where required in existing buildings and structures.
             An automatic sprinkler system shall be provided in existing  guishing systems, distinctive audible, visible alarms and
             buildings and structures where required in Chapter 11.  warning signs shall be provided to warn of pending agent
                                                                     discharge. Where  exposure to automatic-extinguishing
                                                                     agents poses a hazard to persons and a delay is required to
                               SECTION 904                           ensure the evacuation of occupants before agent discharge,
                        ALTERNATIVE AUTOMATIC                        a separate warning signal shall be provided to alert occu-
                      FIRE-EXTINGUISHING SYSTEMS                     pants  once agent  discharge has  begun. Audible signals
                                                                     shall be in accordance with Section 907.5.2.
             904.1 General. Automatic fire-extinguishing systems, other
                                                                     904.3.5 Monitoring. Where a building fire alarm system
             than automatic sprinkler systems, shall be designed, installed,
             inspected, tested and maintained in accordance with the pro-  is installed, automatic fire-extinguishing systems shall be
             visions  of this section and the applicable  referenced stan-  monitored by the building fire alarm system in accordance
             dards.                                                  with NFPA 72.
                                                                  904.4 Inspection and testing. Automatic fire-extinguishing
               904.1.1 Certification of service personnel for fire-extin-  systems shall be inspected and tested in accordance with the
               guishing equipment. Service personnel providing or con-  provisions of this section prior to acceptance.
               ducting maintenance on automatic fire-extinguishing
               systems, other than automatic sprinkler systems, shall pos-  904.4.1 Inspection. Prior to conducting final acceptance
               sess a valid certificate issued by an approved governmen-  tests, all of the following items shall be inspected:
               tal agency, or other approved organization for the type of  1. Hazard specification for consistency with  design
               system and work performed.                                hazard.
             904.2 Where permitted. Automatic fire-extinguishing sys-  2. Type, location and spacing of automatic- and man-
             tems installed as an alternative  to the required  automatic  ual-initiating devices.