FIRE PROTECTION AND LIFE SAFETY SYSTEMS



               ings classified as enclosed parking garages in accordance  be equipped throughout with an approved automatic
               with  Section 406.6 of the  International Building  Code  sprinkler system, or openings shall be provided on
               where either of the following conditions exists:          not fewer than two sides of the story.
                  1. Where the fire area of the enclosed parking garage  903.2.11.1.3 Basements.  Where any portion  of  a
                                                 2
                    exceeds 12,000 square feet (1115 m ).                basement is located more than 75 feet (22 860 mm)
                  2. Where the enclosed parking  garage is located       from openings required by  Section  903.2.11.1, or
                    beneath other groups.                                where  walls, partitions or other obstructions are
                                                                         installed that restrict the application of water from
                       Exception:  Enclosed parking garages located      hose streams,  the  basement shall be equipped
                       beneath Group R-3 occupancies.
                                                                         throughout with an  approved automatic sprinkler
                  903.2.10.1 Commercial parking garages. An  auto-       system.
                  matic sprinkler system  shall be provided throughout  903.2.11.2 Rubbish and linen chutes.  An  automatic
                  buildings used for storage of commercial motor vehi-  sprinkler system shall be installed at the top of rubbish
                  cles where the fire area exceeds 5,000 square feet (464  and linen chutes  and  in their terminal rooms.  Chutes
                   2
                  m ).
                                                                       shall have additional sprinkler heads installed at alter-
               903.2.11 Specific buildings areas and hazards.  In all  nate floors and at the lowest intake.  Where a rubbish
               occupancies other than Group U, an automatic sprinkler  chute extends through a building more than one floor
               system shall be installed for building design or hazards in  below the lowest intake, the extension shall have sprin-
               the  locations set forth  in Sections  903.2.11.1 through  klers installed that are recessed from the drop area of
               903.2.11.6.                                             the chute and protected  from freezing  in accordance
                  903.2.11.1 Stories  without openings. An  automatic  with Section  903.3.1.1.  Such sprinklers shall be
                  sprinkler system shall be installed throughout all  sto-  installed at alternate floors, beginning with the second
                  ries, including  basements, of all  buildings where  the  level below the last intake and ending with the floor
                                                         2
                  floor area  exceeds 1,500 square feet (139 m ) and   above the discharge.   Access to sprinklers  in chutes
                  where the story does not comply with the following cri-  shall be provided for servicing.
                  teria for exterior wall openings:                    903.2.11.3 Buildings 55 feet or more in height. An
                    1. Openings below grade that lead  directly to     automatic sprinkler system shall be installed through-
                       ground level by an exterior stairway complying  out  buildings that  have one or more  stories  with an
                       with Section 1011 or an outside ramp complying  occupant load of 30 or more located 55 feet (16 764
                       with Section 1012. Openings shall be located in  mm) or more above the lowest level of fire department
                       each 50 linear  feet (15  240 mm), or fraction  vehicle access, measured to the finished floor.
                       thereof, of exterior wall in the story on not fewer  Exceptions:
                       than one side. The required openings shall be dis-   1. Open parking structures.
                       tributed such  that the lineal distance between
                       adjacent openings  does  not exceed 50  feet (15     2. Occupancies in Group F-2.
                       240 mm).                                        903.2.11.4 Ducts conveying hazardous exhausts.
                    2. Openings entirely above the adjoining ground    Where required by the International Mechanical Code,
                       level totaling not less than 20 square feet (1.86  automatic sprinklers shall be provided in ducts convey-
                        2
                       m ) in each 50 linear feet (15 240 mm), or frac-  ing hazardous exhaust  or flammable or combustible
                       tion thereof, of exterior wall in the story on not  materials.
                       fewer than one side. The required openings shall  Exception: Ducts where the largest cross-sectional
                       be distributed such that the lineal distance      diameter of the duct is less than 10 inches (254 mm).
                       between adjacent  openings does not  exceed  50  903.2.11.5 Commercial cooking operations. An auto-
                       feet (15 240 mm). The height of the bottom of the  matic sprinkler system shall be installed in commercial
                       clear opening  shall  not  exceed 44 inches (1118  kitchen exhaust hood and duct systems where an auto-
                       mm) measured from the floor.                    matic sprinkler system is used to comply with Section
                    903.2.11.1.1 Opening dimensions  and access.       904.
                    Openings shall  have a minimum dimension  of not   903.2.11.6 Other  required suppression systems. In
                    less than 30 inches (762 mm). Access to such open-  addition to the requirements of Section 903.2, the pro-
                    ings shall be provided for the fire department from  visions indicated in Table 903.2.11.6 require the instal-
                    the exterior and shall not be obstructed in a manner  lation of a fire suppression system for certain buildings
                    such that fire fighting or  rescue cannot be accom-  and areas.
                    plished from the exterior.
                                                                     903.2.12 During construction. Automatic sprinkler sys-
                    903.2.11.1.2 Openings  on one side  only. Where  tems required during construction, alteration and demoli-
                    openings in a story are provided on only one side  tion operations  shall be  provided  in accordance with
                    and the opposite wall of such story is more than 75
                                                                     Section 3314.
                    feet (22 860 mm) from such openings, the story shall