FIRE PROTECTION AND LIFE SAFETY SYSTEMS



              sprinkler system riser room, the door shall be permitted  intended response of subordinate fire protection and life
              to be locked provided  that  the  key is available at all  safety systems shall be verified when required testing of
              times.                                             the initiating system is conducted. In addition, integrated
              901.4.6.2 Marking on access doors. Access doors for  testing  shall be performed in  accordance with Sections
              automatic sprinkler system riser rooms and fire pump  901.6.2.1 and 901.6.2.2.
              rooms shall be labeled with an approved sign. The let-  901.6.2.1 High-rise buildings. For high-rise buildings,
              tering shall be in contrasting color to the background.  integrated testing shall comply with NFPA 4, with an
              Letters  shall  have a minimum  height of 2 inches (51  integrated test performed prior to issuance of the certif-
                                       3
              mm) with a minimum stroke of  /  inch (10 mm).       icate of occupancy and at intervals  not exceeding 10
                                         8
              901.4.6.3 Environment. Automatic sprinkler  system   years, unless otherwise specified by an integrated sys-
              riser rooms and fire pump rooms shall be maintained at  tem test plan prepared in accordance with NFPA 4. If
              a temperature of not less than 40ºF (4ºC). Heating units  an equipment failure is detected during integrated test-
              shall be permanently installed.                      ing, a repeat of the integrated test shall not be required,
                                                                   except as necessary to verify operation of fire protec-
              901.4.6.4 Lighting.  Permanently installed artificial  tion or life safety functions that are initiated by equip-
              illumination shall be provided in the automatic sprin-
              kler system riser rooms and fire pump rooms.         ment that was repaired or replaced.
                                                                   901.6.2.2 Smoke control systems. Where a fire alarm
         901.5 Installation acceptance  testing. Fire detection and
         alarm systems, emergency alarm systems, gas detection sys-  system is integrated  with a smoke control  system as
                                                                   outlined in Section 909, integrated testing shall comply
         tems, fire-extinguishing  systems,  fire hydrant systems,  fire
         standpipe systems, fire pump systems, private fire service  with NFPA 4, with an integrated test performed prior to
                                                                   issuance of the certificate of occupancy and at intervals
         mains and all other fire protection systems and appurtenances  not exceeding 10 years, unless otherwise specified by
         thereto shall be subject to acceptance tests as contained in the  an integrated system test plan prepared in accordance
         installation standards and as approved by the fire code offi-  with NFPA 4. If an equipment failure is detected during
         cial. The  fire code  official shall be notified before any  integrated testing, a repeat of the integrated test shall
         required acceptance testing.
                                                                   not be required, except as necessary to verify operation
           901.5.1 Occupancy. It shall be unlawful  to occupy any  of fire protection or life safety functions that are initi-
           portion of a building or structure until the required fire  ated by equipment that was repaired or replaced.
           detection, alarm and suppression systems have been tested  901.6.3 Records. Records of all system inspections, tests
           and approved.
                                                                 and maintenance required by the  referenced standards
         901.6 Inspection, testing and maintenance.  Fire detection  shall be maintained.
         and alarm systems, emergency alarm systems, gas detection  901.6.3.1 Records information.  Initial records shall
         systems, fire-extinguishing  systems, mechanical smoke    include the name of the installation contractor, type of
         exhaust  systems and  smoke and  heat vents shall be main-  components installed, manufacturer of the components,
         tained in an operative  condition at all times,  and shall be  location and number of components installed per floor.
         replaced or repaired where defective.  Nonrequired fire pro-  Records shall include the manufacturers’ operation and
         tection systems and equipment shall be inspected, tested and  maintenance instruction manuals. Such records shall be
         maintained or removed.
                                                                   maintained for the life of the installation.
           901.6.1 Standards.  Fire protection systems shall  be  901.7 Systems out of service. Where a required fire protec-
           inspected, tested  and maintained in accordance with  the  tion system is out of service, the fire department and the fire
           referenced standards listed in Table 901.6.1.
                                                              code official shall be notified  immediately and,  where
                            TABLE 901.6.1                     required by the fire code official, the building shall be either
           FIRE PROTECTION SYSTEM MAINTENANCE STANDARDS       evacuated or an approved fire watch shall be provided for all
                         SYSTEM                 STANDARD      occupants left unprotected by the shutdown until the fire pro-
                                                              tection system has been returned to service.
         Portable fire extinguishers             NFPA 10
                                                                 Where utilized, fire watches shall be provided with not
         Carbon dioxide fire-extinguishing system   NFPA 12
                                                              less than one  approved means for  notification of the fire
         Halon 1301 fire-extinguishing systems   NFPA 12A
                                                              department and their only duty shall be to perform constant
         Dry-chemical extinguishing systems      NFPA 17      patrols of the protected premises and keep watch for fires.
         Wet-chemical extinguishing systems     NFPA 17A         901.7.1 Impairment  coordinator. The building  owner
                                                                 shall assign an impairment coordinator to comply with the
         Water-based fire protection systems     NFPA 25
                                                                 requirements of this section. In the absence of a specific
         Fire alarm systems                      NFPA 72
                                                                 designee, the owner shall be considered to be the impair-
         Smoke and heat vents                   NFPA 204         ment coordinator.
         Water-mist systems                     NFPA 750         901.7.2 Tag required. A tag shall be used to indicate that
         Clean-agent extinguishing systems      NFPA 2001        a system, or portion thereof, has been removed from ser-
                                                                 vice.
         Aerosol fire-extinguishing systems     NFPA 2010
                                                                 901.7.3 Placement of tag. The tag shall be posted at each
           901.6.2 Integrated testing. Where two or more fire pro-  fire department connection, system control valve,  fire
           tection or life safety systems are interconnected,  the  alarm control unit,  fire alarm annunciator and  fire com-